English
Language : 

XPSAC5121 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – module XPSAC - Emergency stop - 24 V ACDC
Product data sheet
Characteristics
Complementary
Supply frequency
Power consumption in W
Power consumption in VA
Control circuit voltage
Breaking capacity
Breaking capacity
Output thermal current
[Ith] conventional free air thermal current
Associated fuse rating
Minimum output current
Minimum output voltage
Response time on input open
[Ui] rated insulation voltage
Jan 23, 2013
XPSAC5121
module XPSAC - Emergency stop - 24 V AC
DC
Main
Range of product
Product or component
type
Safety module name
Safety module applica-
tion
Function of module
Safety level
Safety reliability data
Type of start
Connections - terminals
Output type
Number of additional
circuits
[Us] rated supply volt-
age
Preventa Safety automation
Preventa safety module
XPSAC
For emergency stop and switch monitoring
Emergency stop
Switch monitoring
Can reach SILCL 3 conforming to EN/IEC 62061
Can reach PL e/category 4 conforming to EN/ISO
13849-1
PFHd = 3.56E-9 1/h conforming to EN/IEC 62061
DC > 99 % conforming to EN/ISO 13849-1
MTTFd = 210.4 years conforming to EN/ISO
13849-1
Unmonitored
Captive screw clamp terminals (2 x 0.5...2 x 1.5
mm²)flexible cable with cable end, with double bezel
Captive screw clamp terminals (2 x 0.25...2 x 1
mm²)flexible cable with cable end, without bezel
Captive screw clamp terminals (2 x 0.14...2 x 0.75
mm²)solid cable without cable end
Captive screw clamp terminals (2 x 0.14...2 x 0.75
mm²)flexible cable without cable end
Captive screw clamp terminals (1 x 0.25...1 x 2.5
mm²)flexible cable with cable end, without bezel
Captive screw clamp terminals (1 x 0.25...1 x 1.5
mm²)flexible cable with cable end, with bezel
Captive screw clamp terminals (1 x 0.14...1 x 2.5
mm²)solid cable without cable end
Captive screw clamp terminals (1 x 0.14...1 x 2.5
mm²)flexible cable without cable end
Relay instantaneous opening 3 NO, volt-free
1 solid state output
24 V DC (- 20...20 %)
24 V AC (- 20...10 %)
50/60 Hz
<= 1.2 W DC
<= 2.5 VA AC
24 V
C300: 1800 VA, AC-15 (inrush) for relay output
C300: 180 VA, AC-15 (holding) for relay output
1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
6 A per relay for relay output
10.5 A
6 A fuse type fast blow for relay output conforming to EN/IEC 60947-5-1, DIN
VDE 0660 part 200
4 A fuse type gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN
VDE 0660 part 200
10 mA for relay output
16 V for relay output
<= 100 ms
300 V (degree of pollution: 2) conforming to IEC 60647-5-1, DIN VDE 0110 part 1
1