English
Language : 

PM-H722LC Datasheet, PDF (1/3 Pages) List of Unclassifed Manufacturers – 0-5Vdc Current transducer
www.sontay.com
Technical Overview
The PM-Hx22 series of current transducers can be used to
monitor motors, pumps or other electrical loads where a
linear voltage output signal is required. The output can be
used to check operating status, failure, wear/strain and
power for consumption analysis. The linear output signal is
produced by the unit which is proportional to the current
passing through the transducer.
Data Sheet Ref: 90501177
Issue: 5.1
PM-Hx22
0-5Vdc Current transducer
Features
•
3 Selectable ranges
•
Load trending
•
Motor control
Specification
Output
Frequency
Insulation class
Accuracy
Response time
Ambient:
Temperature
Humidity
Sensing aperture:
Solid core
Split core
Dimensions:
Sold core
Split core
Protection
Country of origin
0-5Vdc (self powered)
50/60Hz
600Vac RMS
±2% of full scale
2 seconds
-15 to 60°C
0 to 95% non-condensing
19mm dia.
28 x 23mm (self gripping iris)
74H x 76W x 27D mm
74H x 65W x 26D mm
IP20
U.S.A
•
For use inside a separate fire or electrical enclosure
•
For use in a Measurement category III environment,
or less, as per IEC 61010-1:2001
Product Codes
PM-H722LC
Range selectable 0-10 / 0-20 / 0-40A solid core
0-5Vdc output
PM-H722HC
Range selectable 0-50 / 0-100 / 0-200A solid core
0-5Vdc output
PM-H922LC
Range selectable 0-30 / 0-60 / 0-120A split core
0-5Vdc output
International Tel: +44 1732 861225
UK Sales Tel: 0845 345 7253
Page 1
International Fax: +44 1732 861226
UK Sales Fax: 0845 345 7353
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.
90800066 Issue 1