LPN-RK-250 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – dual element, time-delay fuses
Technical Data 1003
Effective March 2017
Supersedes July 2015
LPN-RK — 250 Vac/125 Vdc, 1⁄10-60 A,
dual element, time-delay fuses
Catalog symbols:
• LPN-RK(amp)SP (non-indicating)
• LPN-RK(amp)SPI (indicating)
Description:
Ultimate protection Class RK1 dual element,
current-limiting, time-delay fuses available with
optional open fuse indication. Time-delay – 10
seconds (minimum) at 500% of rated current (8
seconds for 0-30A sizes).
Specifications:
Ratings
• Volts
• 250 Vac
• 125 Vdc
• Amps 1/10-60A
• IR
• 300 kA Vac RMS Sym.
• 100kA Vdc
Agency Information
• UL Listed, Guide JDDZ, File E4273
• CSA Certified, Class 1422-02, File 53787,
Class RK1 per CSA C22.2, No. 248.12
• CE
Catalog no.
LPN-RK-1/10SP
LPN-RK-15/100SP
LPN-RK-2/10SP
LPN-RK-3/10SP
LPN-RK-4/10SP
LPN-RK-1/2SP
LPN-RK-6/10SP
LPN-RK-8/10SP
LPN-RK-1SP
LPN-RK-11/8SP
LPN-RK-11/4SP
LPN-RK-14/10SP
LPN-RK-16/10SP
LPN-RK-18/10SP
LPN-RK-2SP
LPN-RK-9SP
LPN-RK-21/4SP LPN-RK-10SP
LPN-RK-21/2SP LPN-RK-12SP
LPN-RK-28/10SP LPN-RK-15SP
LPN-RK-3SP
LPN-RK-171/2SP
LPN-RK-32/10SP LPN-RK-20SP
LPN-RK-31/2SP LPN-RK-25SP
LPN-RK-4SP
LPN-RK-30SP
LPN-RK-41/2SP LPN-RK-35SP*
LPN-RK-5SP
LPN-RK-40SP*
LPN-RK-56/10SP LPN-RK-45SP*
LPN-RK-6SP
LPN-RK-50SP*
LPN-RK-61/4SP LPN-RK-60SP*
LPN-RK-8SP
* Open fuse indication available by inserting the suffix “I,”
e.g. LPN-RK-50SPI. Requires 75Vac minimum voltage.
Carton quantity
• 10
Features and benefits
• Industry’s only UL Listed and CSA Certified fuse
with a 300 kA interrupting rating that allows for
simple, worry-free installation in virtually any
application.
• Fast short-circuit protection and dual-element,
time-delay performance provide ultimate
protection.
• Reduces existing fuse inventory by up to 33%
when upgrading to Low-Peak fuses.
• Consistent 2:1 ampacity ratios for all Low-Peak
fuses make selective coordination easy.
• Time-delay permits 130% FLA sizing for back-up
motor protection.
• Current-limitation protects downstream
components against damaging thermal and
magnetic effects of short-circuit currents.
• Protects against single-phase motor damage.
• Proper sizing can provide “no damage” Type 2
coordinated protection for NEMA and IEC motor
controllers.