English
Language : 

JPM160 Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – AC/DC Industrial Type 160 Watts
AC/DC Industrial Type
160 Watts
JPM160 Series
•
XPiQ inc.
Intelligent Design Quality Product
CE Marked LVD
•
Low Cost
•
High Reliability
•
Power Factor Corrected
•
Low Ripple Noise
•
Adjustable Output
Specification
Input
AC Input Voltage
Input Frequency
DC Input Voltage
Power Factor
Input Current
Inrush Current
Set-Up time
Rise Time
• 85-264 VAC
• 47-63 Hz
• 120-370 VDC
• 0.98 at 115 VAC, 0.96 at 230 VAC
• 2.8 A max at 115 VAC
• 40 A at 230 VAC cold start
• 600 ms
• 30 ms
Output
Output Voltage
• 3.3 V to 48 V single outputs
Output Power
• 160 Watts, see table
Output Voltage
Adjustment
• +10%, -5%
Minimum Load
• 0 minimum load required
Tolerance
• ±2% max
Line Regulation
• ±0.5%
Load Regulation
• ±1% max, see table
Ripple & Noise
• 100 mV typical, see table
Transient Response • 5% max deviation, 500 µs
recovery time for a 50% load change
Temperature
Coefficient
• 0.05%/°C
Hold Up Time
• 20 ms minimum at 230 VAC
Overvoltage
Protection
• 110-135 %
Overcurrent
Protection
• 130-170%, constant current
auto restart
Overtemperature
Protection
• Shutdown at +95 °C ±5 °C
with auto recovery
General
Efficiency
MTBF
Leakage Current
Isolation Voltage
Size
Weight
• See Table
• 100,000 hrs min
• <2 mA at 240 VAC
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• 199 x 99 x 50mm
• 800 grams
Environmental
Operating
•
Temperature
Cooling
•
Humidity
•
Storage Temperature •
Shock & Vibration •
-10 °C to +60 °C
(see derating curves)
Internal fan
20-90% RH non condensing
-20 °C to +85 °C
10-500 Hz 2G 10 min/cycle
for 60 min each axis
EMC & Safety
Safety Approvals
•
EMI/EMC
•
Immunity & Surge •
UL1950, CSA C22.2 No. 950
per cUL, EN60950, CE Mark LVD
Meets EN61000-3-2, -3, ENV50204,
CISPR22 (EN55022) Class B
Meets EN61000-4-2, -3, -4,
-5, -6 , -8, -11
•
www.XPiQ.com
PH: 508 429.9883
•
FAX: 800 226.2100
Email: sales@xpiq.com