IAC5 Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – 5 VDC SOLID-STATE OPTO-ISOLATED I/O MODULES
IAC5, IDC5, OAC5, ODC5
5 VDC SOLID-STATE OPTO-ISOLATED I/O MODULES
• Available in Standard
or Mini-Pack
Solid state I/O switching modules deliv-
er an electrically clean, photo-isolated,
noise-free "output" interface from
logic level control systems to external
loads such as motors, valves, solenoids,
etc. -- or an "input" interface from the
load or sensors to microprocessor or
computer-based logic level systems.
Designed for long, reliable service in
demanding industrial environments.
Manufactured in Crydom’s ISO 9002
Certified facility for optimum product
performance and reliability.
SYSTEM VOLTAGE 5 Vdc
Model Number
IAC5
MINI-PACK MIAC5
IAC5A
MIAC5A
Voltage Type
AC or DC Input AC or DC Input
Color Code
Yellow
Yellow
IDC5
MIDC5
DC Input
White
IDC5B
MIDC5B
DC Input
White
OAC5
MOAC5
AC Output
Black
OAC5A
MOAC5A
AC Output
Black
ODC5
MODC5
DC Output
Red
ODC5A
MODC5A
DC Output
Red
INPUT SPECIFICATIONS
Voltage Range
90-140 Vac 180-280 Vac 10-36 Vdc
Typical Current @ Rated Voltage
7 mA
5 mA
8 mA
Typical Current @ Maximum Voltage
8 mA
5.5 mA
10 mA
3-32 Vdc
13 mA
15 mA
3-6 Vdc
19 mA
22 mA
3-6 Vdc
19 mA
22 mA
3-6 Vdc
14 mA
18 mA
3-6 Vdc
14 mA
18 mA
OUTPUT SPECIFICATIONS
Load Current Over
Load Voltage Range
.1-100 mA @ .1-100 mA @ .1-100 mA @ .1-100 mA @ .02-3A @ .02-3A @ .02-3A @ .02-1A @
.4-30 Vdc .4-30 Vdc .4-30 Vdc .4-30 Vdc 12-140 Vac 24-280 Vac 5-60 Vdc 10-200 Vdc
Maximum Turn-on Time
Maximum Turn-off Time
Frequency Range
20 ms
20 ms
47-63Hz
20 ms
20 ms
47-63Hz
5 ms
5 ms
-----
1 ms
1 ms
-----
1/2 Cycle
1/2 Cycle
47-63Hz
1/2 Cycle
1/2 Cycle
47-63Hz
0.3 ms
0.3 ms
-----
0.5 ms
0.5 ms
-----
Switching Type
Random Random Random Random
Zero
Zero
Random Random
Max. Surge (non-repetitive)
100mA
100mA
30Vdc
30Vdc 80Apk (1cycle) 80Apk (1cycle) 5A (1 sec) 5A (1 sec)
Max. Off-State Voltage
30Vdc
30Vdc
30Vdc
30Vdc
400Vpk 600Vpk
60Vdc
200Vdc
Notes
1,2,4,6
1,2,4,6
1,2,4
1,2,4
1,2,3
1,2,3
1,2,3
1,2,3
NOTES
©1998 CRYDOM CORP Specifications subject to change without notice.
1. UL recognized.
2. CSA certified.
3. The output of the AC output module is compatible with the input of the AC input module and the output of
the DC output module is compatible with the input of the DC input module.
4. Input modules provide an output that is active low.
5. Output modules can be controlled from active or active high logic.
6. Input will operate on AC or DC voltage.
7. Inductive loads should be diode suppressed for all DC output devices.
FastFax Document No. 301
I/OMOD5V.040898, PAGE 1 OF 2
For recommended applications and more information contact:
USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280
9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: sales@crydom.com
WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191
UK: (44)1202 812300 • fax (44)1202 812340
85, Condor Close, Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU
GERMANY: (49)871 935405 • fax (49)871 935407, Aussere Parkstr.5, D-84032 Altdorf, Germany
9002