B221-30F Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – Fused and non-fused HVAC disconnects
Technical Data 1143
Effective June 2017
Supersedes January 2017
Fused and non-fused HVAC disconnects
Fused disconnect
Non-fused disconnect
Agency Information
• UL® Listed to UL 1429, cUL Certified,
UL Guide WGEW
Conductors - AWG
• 14-3 Cu/Al
Enclosures
• Metallic NEMA 3R housing with weather
resistant coating
Dimensions
• See catalog numbers table
Non-fused disconnect with GFCI receptacle.
Catalog symbol:
• B22__
Description:
Fused and non-fused pullout HVAC disconnects in
NEMA 3R enclosures. Fused versions are available
in 30 and 60 amp ratings with or without self-
testing GFCI receptacles. Non-fused versions are
available in 60 amp versions with or without self-
testing GFCI receptacles.
Specifications:
Ratings
• Volts
• 120 Vac single-phase
• 240 Vac split-phase
• Amps 30 or 60 A
Catalog numbers
• See table on page 2.
Features and benefits
• A/C disconnects meet NEC® Code requirements
under articles 440.14.
• Self-testing GFCI units meet NEC Code
requirements under articles 210.63, 210.8, and
406.8(B)(1).
• NEMA 3R enclosures withstand outdoor
environment.
• Padlockable with two-position pullout handle to
lock safety shield when in the ON position. (Not
available on GFCI or 60 A switched units.) For
added safety, pullout handle can be stored in
the compartment in the OFF position.
Typical applications:
• Residential, light industrial/commercial A/C and
heat pump service
• Spas/whirlpools, swimming pools, pump houses
• Suitable for service entrance equipment
applications with field installed ground bar —
order catalog number DPFG