Hybrid power relays - RHP
s 20 A in a case only 17.5 mm wide
s Service life > 5 million operations at full load
s Silent operation
s Functions: contactor – impulse relay – day/night
contactor
s Clips onto a 35 mm DIN rail
s UL/©UL (listed) approval pending
s NF-USE label pending
s “CE” / Low Voltage Directive conformity
Operating principles
Part numbers (and voltages)
1
Contactor
Contactor control a
Contactor control c
84 138 001
84 138 000
The contactor output is closed when the control voltage is present at the
Impulse relay control a
84 138 101
control input terminals.
Day/night contactor control c
84 138 201
The contactor output is open when there is no voltage at the control input
terminals.
The LED is lit when the output is active.
Input characteristics
Voltage
90…260 V a
Frequency
50 / 60 Hz
0…32 V c
Impulse relay
The impulse relay output changes state on each impulse at the control
input terminals, and remains in that state between each impulse. The
Thresh- OFF control
olds
ON control
Minimum duration
of the control
0 to 46 V a
76 to 260 V a
50 ms
0 to 1 V c
4 to 32 V c
50 ms
output changes state on the rising edge of the control state change.
The pushbutton on the front can be used to select an operating mode:
Output characteristics
Automatic (LED lit): Impulse relay function (Auto)
Voltage
90…260 V a
Forced operation (LED flashing): output closed (ON)
Max. current
20 A in AC1 / AC51 / AC7a
Stop (LED not lit): output open (OFF)
Overload current 20 A
AC-51 : 1,25 x Ie – 60s : 50 - 30
(IEC 60947-4-3)
Day/night contactor
The contactor output is closed when the control voltage is present at the
control input terminals.
The contactor output is open when there is no voltage at the control input
terminals.
The pushbutton on the front can be used to select an operating mode:
Automatic (LED lit): Day/night contactor function (Auto)
Min. current
Frequency
Contact
Number of operations
Leakage current
Acoustic
in steady state
noise
on switching
Terminal block clamping
100 mA in AC1 / AC51 / AC7a
50 / 60 Hz
N.O.
> 5 000 000
< 5 mA
< 35 dB at 1 m
< 50 dB at 0.5 m
2 x 1.5 mm2 with ferrule
4
Forced operation (LED flashing): output closed (ON)
When the control changes state, the day/night contactor reverts to
automatic mode.
Stop (LED not lit): output open (OFF)
capacity:
Terminal tightening torque
Operating temperature
2 x 2.5 mm2 without ferrule
1 x 4 mm2 without ferrule
1 Nm max. M3 screw (IEC60947-1)
-5 °C to +55 °C
Storage temperature
-40 °C to +85 °C
Conformity with standards
IEC/EN 60947-4-3 (industrial environment)
IEC/EN 60669-2-1 (domestic environment)
IEC/EN 60601-1 (medical environment)
IEC/EN 60947-7-1 (connection for industrial env.)
Relative humidity
Casing material
Degree of protection
(according to IEC 60529)
Weight (g)
90 to 95 % without condensation
Self-extinguishing
IP 50 casing
IP 20 terminal block
70 approx.
IEC/EN 60998-2-1 (connection for domestic env.)
Connection
Insulation coordination:
Installation category: 3
Degree of pollution: 3
According to IEC 60664-1: 4KV/3
Breakdown voltage according to IEC/EN60669-2-1:
2 KV/1Min / 1mA / 50 Hz
Insulation resistance according to IEC/EN60669-2-1:
> 5MΩ/500VDC / 1Min
Vibrations according to IEC/EN60068-2-6: frequencies: 10 to 55Hz
amplitude: 0.35 mm
1 3 A1
IN
1 3 A1
90...
260V
2 4 A2
2 4 A2
NI
1 3 A1
90…260 V a/4…32 V c
2 4 A2
LOAD
Dimensions
Standard products
44
60
5,5
17,5
To order, specify:
1 Part number
Example : Solid state relays - RHP - 84 138 001
4/8