English
Language : 

UDM40 Datasheet, PDF (3/11 Pages) List of Unclassifed Manufacturers – Digital Panel Meters Modular Indicator and Controller
UDM40
Measurement accuracy, temp. drifts, min max indications (cont.)
All accuracies and min/max indications refer to an ambient temperature range of 25°C ±5°C, relevant humidity ≤60% and scale ratio (elec-
trical scale / displayed scale) equal to 1. The conversion into °F is obtained acting on the electrical/displayed scale ratio.
Module
Inputs
Type
Accuracy
Temp. Drift Min. Indication Max. Indication
BQ TRX
Ther-
moresis-
tance
-200°C to +850°C Pt100
-328°F to +1562°F Pt100
-200.0°C to +200.0°C Pt100
-328°F to+392°F Pt100
-200.0°C to +200.0°C Pt250
-328°F to +392°F Pt250
-200.0°C to +200.0°C Pt500
-328°F to +392°F Pt500
-200.0°C to +200.0°C Pt1000
-328°F to +392°F Pt1000
-60°C to +180°C Ni100
-76°F to +356°F Ni100
±(0.2%RDG +2DGT)
±(0.2%RDG +4DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +5DGT)
±(0.5%RDG +1DGT)
±(0.5%RDG +2DGT)
BQ TRX
Resis-
tance
0 to 20Ω
0 to 200Ω
0 to 2000Ω
0 to 20.00kΩ
±(0.2%RDG+2DGT)
25% to 110% FS
Ω
±(0.2%RDG+3DGT)
0% to 25% FS
( ) It is possible to modify the decimal point position.
Input impedances and overloads
±150 ppm/°C
±150 ppm/°C
- 200
- 328
- 200.0
- 328.0
- 200.0
- 328.0
- 200.0
- 328.0
- 200.0
- 328.0
- 60
- 76
0
0
0
0
+ 850
+ 1562
+ 200.0
+ 392.0
+ 200.0
+ 392.0
+ 200.0
+ 392.0
+ 200.0
+ 392.0
+ 180
+ 356
20.00 ( )
200.0 ( )
2000 ( )
20.00 ( )
Module
Inputs
Type
Impedance
BQ LSX/
BQ LSE/
BQ LSF
BQ HSX
BQ TRX
Thermo-
couple
BQ TRX
Thermo-
resistance
BQ TRX
Resistance
-200µA to +200µA
-2mA to +2mA
-20mA to +20mA
-200mV to +200mV
-2V to +2V
-20V to +20V
-200mA to +200mA
-2A to +2A
-5A to +5A
-20V to +20V
-200V to +200V
-500V to +500V
-50°C to +760°C
-58 °F to +1400 °F
-200°C to +1260°C
-328 °F to +2300°F
-200°C to +1000°C
-328°F to +1832°F
-50°C to +1750°C
-58°F to +3182°F
-200°C to +400°C
-328°F to +752°F
-200°C to +850°C
-328°F to +1562°F
-200.0°C to +200,0°C
-328°F to +392°F
-200.0°C to +200,0°C
-328°F to +392°F
-60°C to +180°C
-76°F to +356°F
0 to 20Ω
0 to 200Ω
0 to 2000Ω
0 to 20.00kΩ
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
DC/AC
J
J
K
K
E
E
S
S
T
T
Pt100
Pt100
Pt250/Pt100
Pt250/Pt100
Pt1000/Pt500
Pt1000/Pt500
Ni100
Ni100
Ω
≤2,2kΩ
≤22Ω
≤22Ω
≥2,2kΩ
≥200kΩ
≥200kΩ
≤1Ω
≤0.012Ω
≤0.012Ω
≥2MΩ
≥2MΩ
≥2MΩ
ILK <0.5µA
800µA (*)
800µA (*)
90µA (*)
90µA (*)
800µA (*)
800µA (*)
800µA (*)
800µA (*)
800µA (*)
90µA (*)
800µA (*)
90µA (*)
(*) Maximum measuring current generated for resistance equal to 0
Specifications are subject to change without notice UDM40DS 040706
Overload (continuous)
5mA
50mA
50mA
10V
50V
50V
0.8A
7.5A
7.5A
750V
750V
750V
Max 5V
Max 5V
Max 5V
Overloads (1s)
10mA
150mA
150mA
20V
100V
100V
1A
100A
100A
1000V
1000V
1000V
Max 10V
Max 10V
Max 10V
3