OA5669 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Safety relay
Safety relay
OA / OW 5669
• according to EN 50 205, IEC/EN 60 255,
IEC 60 664-1
• with positively driven contacts
• wash proof model as option
• double and reinforced insultaion between
contact sets according to EN 50 178
• low rated power consumption
• high mechanical service life
• compact size, small height
• Approvals: UL, CSA,
TÜV approval: R 9012316
Applications:
ZH1/457 press controls
Switchgear for safety technology
OA / OW 5669
Technical data
Relay type
1. 0 Relay coil
1. 1 Nominal voltage
1. 2 Nominal consumption
DC V
W
OA 5669
5, 6, 12, 20, 24, 48, 60, 110
0,7
2. 0 Contacts
2. 1 Contact arrangement
1 NC / 1NO
2 changeover contacts, 1 No and 1 changeover contact
2. 2 Contact material
AgCdO + 0,2 µm Au; AgNi 10 + 0,2 µm Au optionally + 5 µm Au
2. 3 Rated insulation voltage
AC V
250
Switching voltage min./max.
V
AC/DC 10 / DC 250, AC 400 (AC/DC 100 mV / 60 V) 1)
2. 4 Limiting continuous current
A
2 x 5 (see operating voltage limit curve)
Switching current min./max.
A
10mA3) / 8 (1 mA / 0,3 A)1)
2. 5 Switching power min./max.
VA
3 / 2 000 (1 mVA / 7 VA)1)
Switching power min./max.
W
3 / 200 (1 mW / 7 W) 1) (s. limit curve for arc-free operation)
2. 6 Switching capacity
to IEC/EN 60 947-5-1 AC 15 AC V/A
NC: 230 / 1
NO: 230 / 3
DC 13 DC V/A
NC: 24 / 2
NO: 24 / 2
2. 7 Electrical life 2)
at 1 s On, 1 s Off (s. contacts service life)
AC 230 V 6 A cos ϕ = 1 switching cycles
> 1 x 105 AgNi 10 > 2 x 105 AgCdO
2. 8 Switching frequency max. switching cycles / s
10
2. 9 Response time / Release time ms
≤ 15 / ≤ 12
2.10 Contact force NO / NC
cN
≥ 10 / ≥ 8
3. 0 Other
3. 1 Mechanical life
switching cycles
3. 2 Temperature range
°C
3. 3 Degree of protection, housing
3. 4 Housing
3. 5 Vibration resistance
3. 6 Climate resistance
3. 8 Insolation according to IEC 60 664-1, EN 50 178
Rated insulation voltage
AC V
Contamination level
Overvoltage category
≥ 50 x 106
- 40 ... + 60 mounted without distance (Ith = 2 x 5 A)
IP40 / IP67 IEC/EN 60 529 wash proof
Thermoplast GF, PA
10 ... 55 Hz; 0,35 mm amplitude; 5 g max. IEC/EN 60 068-2-6
40 / 060 / 04 (climate category); A/B/D IEC/EN 60 068-1
double and reinforced insulation
250
2
III
1) Values for AgNi 10-contacts + 5 µm Au
2) 10 A total current at t = 20°C and coil voltage UN
All technical data in this list relate to the state at the moment of edition.
We reserve the right for technical improvements and changes at any time.
3) Typical values
OA/ OW 5669 / 25.02.03 d