|
FCPS-24S6 Datasheet, PDF (1/3 Pages) List of Unclassifed Manufacturers – 6-Amp and 8-Amp 24-Volt Remote Power Supplies | |||
|
July 20, 2004
DN-6927 ⢠E-30
FCPS-24S6 and FCPS-24S8
6-Amp and 8-Amp
24-Volt Remote Power Supplies
Section: Power Supplies
GENERAL
The FCPS-24S6 (6-amp) and FCPS-24S8 (8-amp) are com-
pact, cost-effective remote power supplies with battery charger.
The FCPS-24S6/-24S8 may be connected to any 12- or 24-
volt Fire Alarm Control Panel (FACP) or may be used as a
stand-alone supply. Primary applications include Notification
Appliance (bell) Circuit (NAC) expansion (to support ADA re-
quirements and NAC synchronization) or auxiliary power to
support 24-volt system accessories. The FCPS-24S6/-24S8
provides regulated and filtered 24 VDC power to four notifi-
cation appliance circuits configured as either four Class B (Style
Y) or Class A (Style Z, with ZNAC-4 option module). Alter-
nately, the four outputs may be configured as all non-resettable,
all resettable, or two non-resettable and two resettable. The
FCPS-24S6/-24S8 also contains a battery charger capable of
charging up to 18 AH batteries.
FEATURES
⢠UL-Listed NAC synchronization using System Sensor,
Wheelock, or Gentex âCommander²â appliances.
⢠Cascadable for up to ten power supplies (four for Gentex)
with strobe timing maintained.
⢠Operates as a âsync followerâ or as a âsync generatorâ (de-
fault). See note on page 2.
⢠Contains two fully-isolated input/control circuits â triggered
from FACP NAC (NAC expander mode) or jumpered per-
manently âONâ (stand-alone mode).
⢠Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4
module) NACs.
⢠6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load output,
with 3 amps maximum/circuit, in NAC expander mode (UL 864).
⢠4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous out-
put in stand-alone mode (UL 1481).
⢠Compatible with coded inputs; signals passed through.
⢠Optional power-supervision relay (A77-716B).
⢠In stand-alone mode, output power circuits may be config-
ured as: resettable (reset line from FACP required), non-
resettable, or a mix of two and two.
⢠Fully regulated and filtered power output â optimal for pow-
ering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
⢠Power-limiting technology meets UL power-limiting require-
ments.
⢠Form-C normally-closed trouble relay.
⢠Fully supervised power supply, battery, and NACs.
⢠Selectable earth fault detection.
⢠AC trouble report selectable for immediate or 8-hour delay.
⢠Works with virtually any UL 864 fire alarm control which uti-
lizes an industry-standard reverse-polarity notification cir-
cuit (including unfiltered and unregulated bell power).
⢠Requires input trigger voltage of 9.0 â 32 VDC.
⢠Self-contained in compact, locking cabinet â 15" (38.1 cm)
high x 14.5" (36.83 cm) wide x 2.75" (6.985 cm) deep.
⢠Includes integral battery charger capable of charging up to 18
AH batteries. Cabinet capable of housing 7.0 AH batteries.
S635
California
State Fire
Marshal
7315-0028:225
MEA
299-02-E
⢠Battery charger may be disabled via DIP switch for applica-
tions requiring larger batteries.
⢠Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.1 mm²) wire.
STANDARDS and CODES
The FCPS-24S6/-24S8 complies with the following standards:
⢠NFPA 72 National Fire Alarm Code.
⢠UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
⢠UL 1481 Power Supplies for Fire Alarm Systems (stand-
alone mode).
SPECIFICATIONS
Primary (AC) power:
⢠FCPS-24S6/-24S8: 120 VAC, 60 Hz, 3.2 A maximum.
⢠Wire size: minimum #14 AWG (2.0 mm²) with 600 V insulation.
Control input circuit:
⢠Trigger input voltage: 9 to 32 VDC.
⢠Trigger current: 2.0 mA (16 â 32 V). Per input: 1.0 mA (9 â
16 V).
Trouble contact rating: 5 amps at 24 VDC.
NOTIFIER® is a Honeywell company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
DN-6927 ⢠07/20/04 â Page 1 of 3
|
▷ |