DPB02CM23 Datasheet, PDF (1/4 Pages) List of Unclassifed Manufacturers – Monitoring Relays True RMS 3-Phase, Phase Sequence/Loss - Asymmetry | |||
|
Monitoring Relays
True RMS 3-Phase, Phase Sequence/Loss - Asymmetry
Types DPB02, PPB02
DPB02
PPB02
⢠TRMS 3-phase phase sequence, phase loss and
asymmetry monitoring relays
⢠Detect when all 3 phases are present and have the
correct sequence
⢠Detect if asymmetry level is below the set value
⢠Measure on own power supply
⢠Selection of measuring range by DIP-switches
⢠Adjustable asymmetry on relative scale
⢠Adjustable delay function (0.1 to 30 s)
⢠Output: 8 A relay SPDT N.E.
⢠For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPB02) or plug-in module (PPB02)
⢠22.5 mm Euronorm housing (DPB02)
or 36 mm plug-in module (PPB02)
⢠LED indication for relay, alarm and power supply ON
Product Description
Ordering Key
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss and asymmetry with
built-in time delay function.
Supply ranges from 208 to
480 VAC covered by two
multi voltage relays.
Housing
Function
Type
Item number
Output
Power supply
DPB 02 C M23
Type Selection
Mounting
Output
DIN-rail
Plug-in
SPDT
SPDT
Supply: 208 to 240 VAC Supply: 380 to 415 VAC
DPB 02 C M23
PPB 02 C M23
PPB 02 C M48
Supply: 380 to 480 VAC
DPB 02 C M48
Input Specifications
Output Specifications
Input
L1, L2, L3, N
DPB02: Terminals L1, L2, L3, N
PPB02: Terminals 5, 6, 7, 11
Measure on own supply
Note: Connect the neutral only
if it is intrinsically at the star
centre
Measuring ranges
208 to 240 VAC
177 to 275 âVAC
380 to 480 VAC (DPB02CM48) 323 to 550 âVAC
380 to 415 VAC (PPB02CM48) 323 to 475 âVAC
Ranges
Asymmetry
2 to 22%
of the nominal voltage
Output
Rated insulation voltage
SPDT relay
250 VAC
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
Mechanical life
⥠30 x 106 operations
Electrical life
⥠105 operations
(at 8 A, 250 V, cos Ï = 1)
Operating frequency
⤠7200 operations/h
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Note: The input voltage
must not exceed the maxi-
mum rated voltage or drop
below the minumum rated
voltage reported above.
Specifications are subject to change without notice (18.07.06)