English
Language : 

D38920000024 Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – Repeater
Repeater
Type D 3892 0000
Du line®
Fieldbus Installationbus
• Repeaters make any transmission-distance
possible (cascading of repeaters possible)
• Power-booster for applications with several
Dupline®-supplied units
• Minimized delay (max. 1 Dupline® scan)
• Number of channels adjusted automatically
• H8-housing
• LED-indication for power supply, primary Dupline® OK
and secondary Dupline® (follows Dupline® carrrier)
• Built-in channel generator function for secondary
Dupline®
• AC power supply
Product Description
Ordering Key
D 3892 0000 230
The Dupline® Repeater is used
to increase the distance in a
Dupline® network. Further-
more, it can be used as a
"Power-booster" in sections
with several Dupline®-supplied
units.
Type: Dupline®
H8-housing
Channel Generator (secondary Dupl.)
Power supply
Type Selection
Supply
24 VAC
115 VAC
230 VAC
Ordering no.
D 3892 0000 024
D 3892 0000 115
D 3892 0000 230
Input Specifications
Input
Dielectric voltage
Primary Dupline to
Secondary Dupline®
Primary Dupline®
≥ 2 kVAC (rms)
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21 & 22 230 230 VAC, ±15% (IEC 60038)
115 115 VAC, ±15% (IEC 60038)
24 24 VAC, ±15%
Frequency
45 to 65 Hz
Voltage interruption
≤ 40 ms
Rated operational power
6 VA
Power dissipation
≤7W
Rated impulse withstand
voltage
230 4 kV
115 2.5 kV
24 800 V
Dielectric voltage
Supply - Primary Dupline® ≥ 4 kVAC (rms)
Supply - Secondary Dupline® ≥ 4 kVAC (rms)
Output Specifications
Output
Number of outputs
Output voltage
Current
Short-circuit protection
Output impedance
Sequence time
Distance to transmitters
Secondary Dupline®
1
8.2 VDC
≤ 45 mA
≤ 60 s
≤ 15 Ω
Follows primary Dupline®
100%
General Specifications
Power ON delay
Indication for
Supply ON
Primary Dupline® OK
Secondary Dupline® carrier
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Humidity (non-condensing)
Mechanical resistance
Shock
Vibration
Dimensions
Material
(see "Technical Information")
Weight
≤5s
LED, green
LED, yellow
LED, yellow
IP 40
3 (IEC 60664)
0° to +50°C (+32° to +122°F)
-50° to +85°C (-58° to +185°F)
20 to 80% RH
15 G (11 ms)
2 G (6 to 55 Hz)
H8-housing
485 g
Specifications are subject to change without notice (28.04.03)
1
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group