ACM-8RF Datasheet, PDF (1/2 Pages) List of Unclassifed Manufacturers – RELAY MODULE FOR USE WITH MS-9200 MS-9200UD MS-9600 AND MS-5210UD
www.firelite.com
July 13, 2004
DF-51555 • B-500
ACM-8RF
Relay Module for use with MS-9200,
MS-9200UD, MS-9600 and MS-5210UD
Section: Annunciators
GENERAL
The ACM-8RF is a relay module in the Fire•Lite AFM Se-
ries of annunciators. It provides the MS-9200, MS-9200UD
and MS-9600 Fire Alarm Control Panels and MS-5210UD
10-zone Fire Alarm Control/Communicator with relay-by-
zone capability for elevator recall, HVAC control, etc. The
ACM-8RF provides eight (8) Form-C mappable relays with
contacts rated at 5 amps. The ACM-8RF mounts remote
from the MS-9200, MS-9200UD, MS-9600 and MS-5210UD
in an ABS-8RF enclosure.
Up to 32 ACM-8RF relay modules may be installed on the
panel’s EIA-485 circuit.
S624
CS68/CS702
MEA
122-96-E, Vol. II
California
State Fire
Marshal
7120-0075:178
FEATURES
• Provides eight Form-C relays with 5-amp contacts.
• Up to 32 ACM-8RFs may be installed on the MS-9200,
MS-9200UD, MS-9600 and MS-5210UD’s EIA-485 se-
rial output.
• Mounts remotely in ABS-8RF enclosure.
• Requires only two wires for communication and two for
power.
• Removable terminal blocks for ease of installation and ser-
vice.
• DIP switch selectable memory mapping of relays.
MOUNTING
The ACM-8RF will only mount to an ABS-8RF annunciator
surface-mount backbox with blank faceplate.
OPERATION
Communication between the Control Panel and the ACM-
8RF is accomplished over a two-wire EIA-485 serial inter-
face. This communication, to include the wiring, is super-
vised by the fire alarm control panel. Power for the relay
module is provided via a separate power loop from the con-
trol panel which is inherently supervised (loss of power also
results in a communication failure at the control panel).
RELAY MAPPING
The ACM-8RF’s relays follow the status of the 56 software
zones of the MS-9200, the 99 software zones of the MS-
9200UD and MS-9600 or the 10 Initiating Device Circuits
(IDCs) of the MS-5210UD. For full relay-by-zone capability
with the MS-9200 (i.e., 56 software zones), a minimum of
seven ACM-8RFs are required (alarm only). For full Relay-
By-Zone capability with MS-9200UD and MS-9600, a mini-
mum of 13 ACM-8RF’s are required(alarm only). For full
MS-5210UD relay-by-zone capability (i.e., all 10 zones), a
minimum of two ACM-8RFs are required (alarm only).
Consult the ACM-8RF installation manual for application-
specific details.
Fire•Lite® Alarms is a Honeywell company.
This document is not intended to be used for installation purposes. We try to keep
our product information up-to-date and accurate. We cannot cover all specific
applications or anticipate all requirements. All specifications are subject to
change without notice.
For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford,
Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105.
ACM-8RF
Made in the U.S.A.
DF-51555 • 07/13/04 — Page 1 of 2