English
Language : 

104-PR Datasheet, PDF (4/4 Pages) ETAL Group – Motors, transformers, solenoids, printed circuit boards, hand-held machines and appliances, marine applications, caravans.
Thermal Overcurrent Circuit Breakers 104/105/106-...
Typical time/current characteristics at +23 °C/+73.4 °F
10000
1000
0.05 - 6 A
7 - 10 A
Accessories
Water splash cover (transparent)/knurled nut assembly
(type 106-... only)
X 201 285 01 (IP64)
100
1
10
1
Knurled nut 3/8", plastic (standard)
Y 307 117 02
ø15
3
.591
.118
0.1
1
2
4 6 8 10 20
30
… times rated current
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the
circuit breaker current ratings by the derating factor shown below. See also
section Technical information.
Ambient temperature °F -4 +14 +32 +73.4 +104 +122 +140
°C -20 -10 0 +23 +40 +50 +60
Derating factor
0.76 0.84 0.92 1 1.08 1.16 1.24
3/8-27UNS-2B
Hex nut 3/8", nickel-plated brass
Y 300 192 01
3/8-27UNS-2B
2.5
.098
SW14
.551
This
is
a
metric
design
and
millimeter
dimensions
take
precedence
(
mm
inch
)
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
4
www.e-t-a.de