E-1048-S602 Datasheet, PDF (2/4 Pages) ETAL Group – Optimum load protection. Available in current ratings of 0.5 A; 1 A; 2 A; 4 A. No derating required over entire temperature range!
Solid State Remote Power Controller E-1048-S6...
Technical description
Dimensions
At the appropriate input level (>8.5 V), the opto decoupled input in the
SSRPC will switch on a power transistor to connect the load to the
plus pole of the load circuit supply (US).
The transistor will switch off when
- the control voltage (UE) is removed
- there is a short-circuit/overload in the load circuit.
Status indication is provided by two LEDs (red and green).
Thermal-magnetic style overload protection occurs at approx.
1.5 times rated current. See time/current characteristic curves.
The SSRPC is fitted with blade terminals DIN 46244-A6.3-0.8 and
is suitable for plug-in mounting with various E-T-A sockets (see
Accessories).
Control circuit
ON condition:
If a voltage higher than 8.5 V is applied to the input terminals (-IN,
+IN), the control current (from the PLC) will flow through the opto
coupler. The output transistor will be conductive, the green LED will
be lighted.
OFF condition:
A control voltage lower than 5 V will switch the output transistor off.
Load circuit
The load circuit switches depending on the control signal (“0” or “1”).
It is electronically monitored for faults. In the event of a short-circuit
the circuit is disconnected after max. 250 µs whilst upon inadmissible
overload it is disconnected according to the time/current curves
shown.
Fault indication output
The fault indication circuit (F+, F-) is opto decoupled from the load
and control circuit.
In the OFF condition, this circuit will provide wire break indication,
with the transistor output being open.
In the ON condition, the circuit will provide short-circuit and overload
monitoring and indication.
Visual fault indication by red LED.
Status indication
60
2.36
2573641
reverse plug-in
protection
LED green
6.8
6x6.8=40.8
.267
6x.267=1.60 50
1.97
LED red
blade terminals
DIN 46244-6.3-0.8
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Typical time/current characteristics (TA = 25 °C)
0.5 A and 1 A
1000
100
Status indication
non-conductive, no duty
Fault indication output
LED
(opto coupler)
green red
5
conductive, normal duty
overload or short circuit at the output
(and with option wire break indication in
ON condition)
wire break, in the OFF position
Connection diagram
10
1
current limitation
0.1
2 A and 4 A
IN
10
20
30
I (A)
1000
E-1048-S600
2
IN+
control circuit
IN- 5
7
F+
fault output
F- 3
green
control and
monitoring
electronics
red
2
1 +US
4Q
6 -US
www.e-t-a.de
100
10
1
current limitation
0.1
IN
20
40
60
80
I (A)
1646