English
Language : 

SVS14 Datasheet, PDF (1/6 Pages) ETAL Group – Systematic integration of power distribution, protection and signalling functions
Power distribution system SVS14
Description
The power distribution system SVS14-10 optimises DC 24 V distribution
on the field level in automated process control, industrial production
and chemical plants. The system holds an integral ammeter (display
25 A) for the total current and offers ten ways for electronic and
thermal-magnetic circuit breakers including group signalling. It allows
protection of transformers, actuators, solenoids, peripheral PLCs,
intelligent terminals etc. on the field level. Particularly for systems with
a great number of sensors/actuators the SVS14 power distribution
system enables a space-saving and cost-effective design of protection
control cabinets.
Any load circuit which might be disconnected due to overload or short
circuit generates a single signal which will be summarised in a group
signal directly on the power distribution system and which will be fed
back directly to control.
SVS14-10-C22-A01
The SVS14 is a track-mountable system and accommodates 10 electronic
or thermal-magnetic circuit breakers. All terminals (entry line DC +24 V,
GND (-) for self-supply, load outputs L(+) and group signalling are
standard screw terminals.
Technical data (Tamb = 25 °C, UB = DC 24 V)
The SVS14 accommodates the following E-T-A types:
Electronic circuit breaker
ESS20-003..
Electronic circuit protector
ESX10-103..
Thermal-magnetic circuit breaker
2210-S211, 3600-P10,
3900-P10
Application
Modular power distribution system for current limited DC 24 V -
applications. In the event of current supply rated higher than 25 A
and with battery-buffered supplies please use a 25 A protection
with medium delay trip curve (e.g. E-T-A type 4220-T, 2210-T).
Supply
Features
l Systematic integration of power distribution, protection
and signalling functions
l Power distribution and selective protection of DC 24 V loads
from a single source
l Group signalling pre-wired
l Integral Si contact (per way) for free slots, Si circuit can be closed.
Rated voltage: DC 24 V (18...32 V)
Total current: max. 25 A
DC 24 V (+) terminal block X21 2+/1+
DC 24 V (-) terminal block X21 2-/1-
Terminals: 4-pole screw terminals
cable cross section max. 16 mm2
(with and without wire end ferrule)
Gauge: Ammeter DIN 48, current rating 25 A
(moving-iron instrument, 1.5 %)
F ways
Ordering information
Ten ways for circuit breaker, prepared for types
ESS20-003, ESX10-103, 2210-S211, 3600-P10, 3900-P10
SVS14-10 / 10-way / F1… F10 = terminal X1+/X1-…X10+/X10-
Type
Load outputs per way (F1...F10)
SVS14 Power distribution system for ESS20-003, ESX10-103
l Short circuit limited DC 24 V applications
l Max. 25 A cont. load
l Integral group signalling terminals S2 S1, DC 24 V / max. 0.5 A to
be protected separately
l Integral Si contact (per way) for free slots, Si circuit can be closed
l Including 2 end pieces X 222 004 01
Version, max. number of circuit breakers
10 10 circuit breakers (F1...F10)
Population option, load output
Rated voltage: DC 24 V (18...32 V)
Current: max. 8 A per way1)
Number: 1 protected load output L(+) (at way F1 on
terminal X1+)
1 minus return load (at way F1 on terminal X1-)
Terminals: 2-pole double level terminal with screw terminal
cable cross section max. 4 mm2 (with and
without wire end ferrule)
Signalling
C22 Fully populated with pcb screw terminals (double level)
Signal terminal X31 (S2, S1) for group signal
(max. 4 mm2, without wire end ferrule)
Rated voltage: DC 24 V (18...28 V)
Integral ammeter
Total current: max. 0.5 A
A01 Ammeter 90° to rail
(vertical mounting position)
(Caution: use external protection 0.5 A/fast)
S1 External supply possible + DC 24 V for
6
(25 A / class 1.5 % / 48x48)
signalling
A02 Ammeter 0° to rail
S2 Signal output, group signal of ways F1…F10
(horizontal mounting position)
Terminals:
2-pole double level terminal with screw terminal
(25 A / class 1.5 % / 48x48)
cable cross section max. 4 mm2
Special version
(with and without wire end ferrule)
Sxxx
1) When mounted side-by-side and full population with circuit breakers type ESS20, ESX10,
SVS14 - 10 - C22 - A01 Ordering example
2210, 3600 and 3900 with current rating 10 A, each device should carry only 80 % of its
rating.
Accessories: external jumper and end piece see page “Accessories“
1646
www.e-t-a.de
1