SVS04 Datasheet, PDF (1/10 Pages) ETAL Group – Power Distribution System
Power Distribution System SVS04
Description
The SVS04 power distribution system for symmetrical DIN rail
mounting is designed to distribute power from a switch-mode power
supply to 4 or 8 channels. Selective protection of the load output
circuits is provided by the plug-in type circuit breakers installed. With
a max. load current of 8A per channel and a max. total current of
40A the SVS04 provides ease of wiring in short circuit current limited
DC24V applications. Five protected “L+” load outputs per way and
15 or 30 minus terminals significantly reduce wiring time enormously.
Electronic circuit breaker ESS20-003, electronic circuit protector
ESX10-103 and thermal-magnetic circuit breakers 2210-S21 are all
suitable for use with the SVS04, plugging directly into the sockets
provided for each of the 4 or 8 outputs.
SVS04-08-...
Ordering information
Type
SVS04 power distribution system for types ESS20-003, ESX10-103,
2210-S21
l for short circuit current limited DC 24 V applications
l max. 40 A continuous load
l one integral circuit breaker (CB1): overcurrent protection of group
signalisation, red LED flashes upon trip of CB1
l including 1 insulated wire bridge Y 303 881 08
l accessories: jumper SB-S11-P1-01-1-1A
for unused ways, please order separately
Version, max. number of circuit breakers on the power
distribution system
04 4 circuit breakers F1...F4)
08 8 circuit breakers (F1...F8)
Fitted versions
B10 standard: fitted with screwless spring-loaded
terminals (max. 2.5 mm2, without wire end ferrule)
B20 fitted with plug-in type screw terminals (max. 2.5 mm2,
without wire end ferrule)
C10 fitted with pcb terminals, spring-loaded terminals
(max. 2.5 mm2, without wire end ferrule)
Minus terminals
­ – 15 minus terminals
K01 30 minus terminals (only for SVS04-08)
Special marking
SB01 with marked terminals
entry line +++/---
remaining terminals 1/2/3/4/5
SVS04 - 04 - B10 - K01 - SB01
Technical data
DC 24 V supply
DC 24 V terminals, 2x3 terminals
(screwless terminals max. 10 mm2), for current supply
- DC 24 V (+) = (X21) +/+/+
- DC 24 V (-) = (X21) -/-/-
Integral loop-through, for wiring and additional
connection of an external buffer module.
F positions
Number of ways for circuit breakers, suitable
for types ESS20-003, ESX10-103, 2210-S21
SVS04-04... F1...F4 = terminals X1...X4
SVS04-08... F1...F8 = terminals X1...X8
Plug jumper SB-S11-P1-01-1-1A into unused ways
(please order separately, see accessories)
Load outputs
5 x L+ protected per position F1…F4 (F1…F8), led
through terminals X1…X4 (X1…X8), max. 2.5 mm2
load current max. 8 A per position
Signalisation
signalisation terminal X31, 5-pole, max. 2.5 mm2
+: DC 24 V feed from terminal X21, protected by
integral circuit breaker CB1
total current max. 0.5 A
group signalisation:
S: line feed DC 24 V, insert insulated wire bridge
Y 303 881 08 (bulk shipped) between + and GR
AS: output of group signalisation
two-group signalisation
GR: line feed, insert insulated wire bridge Y 303 881 08
(bulk shipped) between + and GR
AS: output group A (X5…X8)
B: output group B (X1…X4)
Minus terminals
3 x 5 terminals (X22, X23, X24) or
6 x 5 terminals (X22, X23, X24, X25, X26, X27): version K01
6
Termination
For signalisation, load outputs and minus terminals:
B10: screwless spring-loaded terminals max.
2.5 mm2, with integral test socket
B20: plug-in type screw terminals max 2.5 mm2,
with integral test socket
C10: pcb terminal/spring-loaded terminal max. 2.5 mm2,
with integral test socket
General data
l protection class to DIN 40050: IP20
l insulation co-ordination to IEC 60934: 0.5 kV
l pollution degree 2
l dielectric strength AC 500 V
l temperature range: 0…50 °C (without condensation)
l for symmetrical DIN rail mounting EN50022 – 35 x 7.5
l dimensions: see dimensional drawings