English
Language : 

SMP11 Datasheet, PDF (1/6 Pages) Vishay Siliconix – Surface Mount TRANSZORB Transient Voltage Suppressors
Switched mode power supply for DIN rail mounting type SMP11 DC24V/10A
Description
Switched mode power supply for rail mounting, wide range voltage
input, high efficiency, integral active power factor compensation
(PFC), parallel mode for performance improvement
Features and Benefits
l Wide range voltage input from AC 88 to 264 V
l Efficiency up to 93%
l Integral power factor compensation
l Parallel mode for performance improvement (selectable by switch)
Typical applications
Process control, industrial switch- and controlgear, machine
construction, telecommunication systems
SMP11-DC24V/10A
Version L20
Technical data (TU = 25°C, UB = AC 100 V...240 V, I0 = 10 A)
Order numbering code
Operating data
Input voltage ranges UE AC 88…264 V
Type No.
SMP11 S ingle phase switch-mode power supply for rail mounting
Operating voltage range AC 100...240 V
UB
Connector design
Effective output
240 W
L pcb mounting (preferred type)
S plug-in type
Terminal design
20 screw terminals
Output voltage
Output voltage UO
24 V SELV
Output current rating IO 10 A
3
Efficiency
91 % min. / 93 % typically
General data
DC24V DC 24 V
Switching frequency
typically 90 kHz
Output current
10 A
SMP11–L20-DC24V-10A ordering example
Approvals
Insulation voltage
between
input and output
input and
protective conductor
output and
protective conductor
Insulation resistance
AC 3000 V, DC 4242 V
AC 1500 V, DC 2121 V
AC 500 V, DC 710 V
100 MΩ (DC 500 V) between
input and output
Approval
authority
UL
TÜV
Rheinland
Standards
UL508, CSA C22.2 No. 107.1 (listed)
UL 60950-1, CSAC22.2 No. 60950-1 (recognized)
EN 60950-1
Ambient temperature
Derating factor
(see curve)
Storage temperature
Relative humidity
MTBF to Bellcore, ed. 6
-40 °C…+71°C
2.5 % / °C
-40 °C…+85 °C
20…90 % RH
481,000 hours at 40°C, GB
EMC
EN 61000-6-3, EN 61000-6-2, EN 61204-3
Max. altitude in
operation to IEC
60068-2-13
Cooling
5000 m above sea level
by convection
Mounting direction
wall-mounted (see dimensions)
Pollution degree
2
Input circuit
Input rated voltage
AC 100...240 V
Input voltage range
AC 88…264 V
Input current
Max. input current
Supply frequency
1.15 A typically at UB = AC 230 V
2.3 A typically at UB = AC 115 V
3.2 A typically at UB = AC 88 V
47...63 Hz
Inrush current
at AC 115 V
at AC 230 V
24 A max.
48 A max.
1646
www.e-t-a.de
1