E-1048-S7 Datasheet, PDF (1/4 Pages) ETAL Group – Optimum load protection because a range of current ratings is available
Solid state remote power controller E-1048-S7...
Description
The E-T-A solid state remote power controller for PLC outputs
E-1084-S7... is a transistor switch with integral protection and
signalling functions. It is used in applications where the existing
PLC output power is not sufficient. In addition the device provides
protection against short circuit and overload as well as a monitoring
function with regard to wire break. The solid state remote power
controller E-1048-S7.. reduces the number of components such as fuses
and relays and avoids the use of expensive powerful output cards.
The devices are operated on a power distribution module 17plus
and they also fit into the smart power distribution system SVS16.
The E-1048-S7.. easily allows control, protection and load circuit
diagnosis and offers reduced wiring efforts.
E-1048-S7xx
Applications
Automation and process control
- Coupler component for cost-effective power gain at PLC outputs
- Optimum protection of every single load by load circuit monitoring
Protection and control for fast switching operations with:
- motors
- magnetic valves
- resistive loads
- signalling and monitoring lamps
Technical data (Tamb = 25 °C, at UN)
Load circuit
Operating voltage UB
DC 24 V (18...32 V)
Current ratings IN
1; 2; 4; 5 A
Quiescent current IS
typically 0.5 mA
Min. load current
Version700:
wire break “OFF” condition: Rload > 500 KΩ
Features
Option: wire break in “OFF” and “ON” condition:
wire break “OFF” condition: Rload > typically 500 kΩ
l Optimum load protection because a range of current ratings is
wire break “ON” condition: Iload < typically 130 mA (1 A unit)
available
Iload < typically 500 mA (2/4/5 A unit)
l No derating over the entire temperature range
Voltage drop UDSmax
0.1 V
l Fast short circuit disconnection with simultaneous short-circuit
limitation
l Time-dependent overload disconnection (trip curve similar to
thermal-magnetic circuit breakers)
Trip times tON/tOFF
Overload disconnection
Short circuit current
OFF delay
typically 5 ms / 1.5 ms
1.5 (±-0.3) x IN after approx. 200 ms
max. 50 A L/R = 2- 3 ms
max. 180 A L/R = 0 ms
typically 200 ms
l Remotely controllable
l Error message: LED and signal output indicate overload/short Control input IN+
circuit and wire break in the “OFF” condition (version 700), wire Control level
between IN+ and GND
break in “OFF” and “ON” condition: (type: 702)
Voltage controlled
DC 0 V < low level < 5 V
l Physically isolated fault indication
l Compact enclosure
l Plug-in design to fit into power distribution module 17plus and
Input UE
DC 8.5 V < high level < 32 V
Input current IE
1...10 mA (8.5 V...32 V)
Max. switching frequency fmax 100 Hz
power distribution system SVS16
Error signal output
Relay contact
max. DC 30 V / 0.5 A
5
(potential-free signal contact) min. DC 10 V / 10 mA
Order numbering code
General data
Type No.
E-1048
solid state remote power controller for PLC outputs
Version
S700 with wire break monitoring in OFF condition (standard)
S702 with permanent wire break monitoring
S703 without wire break monitoring
Rated voltage
DC 24 V DC 24 V (standard)
Current ratings
1.0 A
2.0 A
4.0 A
5.0 A
Housing material
moulded
Operating temperature 0…60°C
Storage temperature
-40...70°C
Blade terminals
6.3 mm to EN 60934-6.3-0.8
Humidity
96 hours at 95% RH, 40 °C
to IEC 60068-2-78,-Cab
climate class 3K3 to EN60721
Vibration
3g test to IEC 60068-2-6, test Fc
Shock 30 g/11 ms halfsine to EN60068-2-7
Protection class
housing IP30 DIN40050
terminals IP00 EN 40050
E-1048 - S700 DC 24 V 1.0 A ordering example
EMC requirements
noise emission: EN 61000-6-3
noise immunity: EN 61000-6-2
Insulation resistance
>100MΩ (DC500V) auxiliary contact
to
LINE, LOAD, GND and IN+ (bridged)
Dielectric strength test voltage AC 500 V, auxiliary con-
tact to LINE, LOAD, GND and IN+
(bridged)
Dimensions (w x h d)
12.5 x 70 x 60 mm
Mass
approx. 33g
1646
www.e-t-a.de
1