English
Language : 

8345-B Datasheet, PDF (1/10 Pages) ETAL Group – In the business fields Communication and Transport: power supplies, switchgear, instrumentation and process control engineering
Magnetic and Hydraulic-Magnetic Circuit Breaker 8345-...
Description
Single or multipole hydraulic-magnetic circuit breakers with trip-free-­­
mechanism and toggle actuation. A choice of switching characteristics
ensures suitability for a wide range of applications. Industry standard
dimensions and panel mounting. Auxiliary contacts optional. Low
temperature sensitivity at rated load.
Approved to CBE standard EN 60934 (IEC 60934) S-type HM CBE.
Typical applications
In the business fields Communication and Transport: power supplies,
switchgear, instrumentation and process control engineering.
1
8345
1-pole
2-pole
Standard current ratings and typical internal resistance values
Current
rating (A)
0,05
0,1
1
2
3
5
10
15
20
25
30
40
50
60
80
100
125
Trip curves and internal resistance (Ω) per pole
F1
F2
K1, M1, T1 K2, M2, T2
275
152
531
542
58
36,5
129
127
0,578
0,347
1,10
1,08
0,144
0,0959
0,295
0,291
0,0644
0,0477
0,121
0,118
0,0250
0,0192
0,0437
0,0449
0,00901
0,00714
0,0147
0,0133
0,00597
0,00483
0,00794
0,00794
0,00468
0,00410
0,00597
0,00597
0,00410
0,00385
0,00456
0,00456
0,00385
0,00371
0,00458
0,00458
0,00371
0,00371
0,00373
0,00373
0,00358
0,00358
0,00335
0,00335
---
---
0,00333
0,00333
---
---
0,00325
0,00325
---
---
0,00316
0,00316
---
---
0,00314
0,00314
Interrupting capacity to EN 60934, CCC, UL 489, UL 1077
IEC 60934 / CCC (3-pole) – test series E:
voltage
number of
poles
IN max. (A)
Icn (A)
DC 80 V
1+2
0.02...125
10 000
AC 240/415 V
AC 240 V
1 - (6)
1
0.02...80
0.02...20
6 x IN
5 000
UL 489 – test sequence Z:
voltage
number of
poles
IN max. (A)
Icn (A)
DC 80 V
1+2
0.5...125
10 000
AC 120 V
1
0.5...80
5 000
AC 120/240 V
1 (2)
0.5...80
5 000
AC 240 V
1
0.5...20
5 000
UL 1077:
voltage
number of
poles
IN max. (A)
Icn (A)
DC 80 V
1+2
0.02...125
10 000
AC 277/480 V
1-6
0.02...70
5 000
Technical data
Voltage rating
3 AC 415 V; AC 277/480 V;
AC 120/240 V; AC 240 V; DC 80 V
(higher DC voltages to special order)
Current rating range
0.05...125 A single and multipole
higher ratings upon request
Auxiliary circuit
AC 240 V 6 A
DC 28 V 3 A
DC 65 V 1 A
DC 80 V 0.5 A
Typical life
10,000 operations at 1 x IN
Ambient temperature
-40...+85 °C (-40...+185 °F)
Insulation co-ordination
(IEC 60664)
2.5 kV/2
reinforced insulation in operating area
Dielectric strength
operating area
test voltage AC 3,000 V
Line to Load
test voltage AC 1,500 V
pole to pole (2- and 3-pole) test voltage AC 1,500 V
main to auxiliary circuit test voltage AC 3,000 V
switching to trip circuit test voltage AC 1,500 V
(version -X)
Insulation resistance
> 100 MΩ (DC 500 V)
Degree of protection
(IEC 60529)
operating area IP40
terminal area IP00
Vibration
upside down:
directions 1, 2, 3, 4, 5:
with curves F1, F2:
10 g (57-2000 Hz) ± 0,76 mm (10-57 Hz)
at 0.9 IN
10 g at 1 x IN
10 g at 0.8 x IN in all planes.
(57-2000 Hz) ± 0.76 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
directions 1, 2, 3, 4, 5:
direction 6:
with curves F1, F2:
100 g (11 ms) at 1 x IN,
100 g (11 ms) at 0.8 x IN,
100 g (11 ms) at 0.8 x IN
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass
approx. 90 - 120 g per pole
depending on version
1651
www.e-t-a.de
1