English
Language : 

808-H Datasheet, PDF (1/2 Pages) ETAL Group – Printed circuit boards and components, safety and control systems
Magnetic Overcurrent Circuit Breaker 808-...
Description
Single pole miniaturised magnetic circuit breakers with unique
high-­­speed operating mechanism and push/pull on/off manual
actuation. Fitted with electrically separate excitation and switching
circuits, and one pair of auxiliary contacts which close when the
main circuit is open. Also suitable for impulse operation. Designed for
printed circuit board mounting. Low temperature sensitivity.
Typical applications
Printed circuit boards and components, safety and control systems.
1
Ordering information
808
Type No.
808 fast-acting
Manual release
H manual release facility
Current ratings
0.01...5 A
808 - H - 5 A ordering example
Preferred types
Preferred types Standard current ratings (A)
0.02 0.05 0.1 0.3 0.4 0.5 0.6 1 2 3 5
808-H-
x x xxxxxxxxx
Standard current ratings and typical internal resistance values
Current
rating (A)
0.01
0.02
0.03
0.04
0.05
0.08
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Internal
Current
resistance (Ω) rating (A)
625
0.8
170
0.9
77
1
47
1.2
29.2
1.5
10.3
2
5.6
2.5
1.65
3
0.89
3.25
0.39
4
0.28
4.5
0.198
5
0.143
Internal
resistance (Ω)
0.096
0.085
0.073
0.050
0.031
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
Approvals
Technical data
Voltage rating
Current ratings
Max. continuous load
excitation circuit (2-3)
Max. continuous load
switching circuit 6-7
auxiliary circuit 4-5
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664-1)
Dielectric strength
(UL 1077)
operating area
excitation to
switching circuit
excitation to
auxiliary circuit
Insulation resistance
Interrupting capacity
(o-o-o)
Interrupting capacity
(UL 1077)
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
DC 24 V (higher voltages to special order)
UL: AC 120 V; DC 60 V
0.01...5 A
(higher current ratings to special order)
2.65 x IN
5A
6,000 operations
at 5 A for switching circuit
-30...+70 °C (-22...+158 °F)
rated impulse
withstand voltage
1.5 kV
pollution
degree
2
test voltage
AC 1,240 V
AC 1,240 V
AC 1,240 V
> 100 MΩ (DC 500 V)
100 A
2,000 A AC 120 V
1,000 A DC 60 V
operating area IP30
terminal area IP00
3 g (57-500 Hz), ± 0.23 mm (10-57 Hz),
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms)
to IEC 60068-2-27, test Ea
48 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 10 g
Authority Standard
UL
UL 1077
C22.2 No 235
CSA
C22.2 No 235
Rated voltage
AC 120 V
DC 60 V
AC 120 V
DC 60 V
AC 120 V
DC 60 V
Current ratings
0.006 A…8 A
0.006 A…8 A
0.006 A…5 A
0.006 A…8 A
0.01...5 A
0.01...8 A
1646
www.e-t-a.de
1