English
Language : 

4230-T1 Datasheet, PDF (1/12 Pages) ETAL Group – Protection of cables, motors, generators and transformers, thyristors and silicon rectifiers
Thermal-magnetic Miniature Circuit Breaker 4230-T...
Description
Single pole and multipole thermal-magnetic miniature circuit breakers
(MCBs) in accordance with EN 60947-2, UL 1077 and UL 489 for
DIN rail mounting, with toggle actuation, visual status indication and
high rupture capacity. A positively trip-free snap action mechanism
ensures reliable switching behaviour. A range of trip characteristics
and add-on modules allow a great variety of applications.
Typical applications
Protection of cables, motors, generators and transformers, thyristors
and silicon rectifiers. Protection of computers and their peripheral
equipment, industrial process control systems, telecommunications
equipment, power supplies.
1
4230-T...
UL 489 version
IEC/EN60947-2 & UL1077 version
Technical Data
Voltage rating and current rating range
to IEC/EN 60947-2 1-pole: AC 240 V; 1 A…63 A;
2, 3, 4-pole: AC 415 V, 1 A…63 A;
1-pole: DC 80 V, 1 A...63 A
2-pole: (2 poles connected in series)
DC 125 V, 1...63 A
to UL 1077 1-pole: AC 277 V; 1 A…63 A;
2, 3, 4-pole: AC 480Y/277 V, 1 A…63 A;
1-pole: DC 60 V; 1 A...63 A;
2-pole (2 poles connected in series):
DC 125 V; 1 A...63 A;
to UL 489 1-pole: AC 120 V; 1A…63 A;
2, 3-pole: AC 240 V, 1 A…63 A;
1-pole: AC 277 V; 1 A…32 A;
2, 3-pole: AC 480Y/277 V; 1 A…32 A;
1-pole: DC 60 V; 1 A…63 A;
2-pole (2 poles connected in series);
DC 125 V; 1 A…63 A;
Typical life
Mechanically
20,000 cycles
Electrically 6,000 cycles
Approvals
Approval Standard Rated voltage Current ratings
authority
TÜV
IEC/EN
AC 240/415 V 1...63 A
60947-2 DC 80 V
1...63 A (1-pole)
DC 125 V
1...63 A (2 poles in
series)
UL
UL 1077 / AC 480Y/277 V 1...63 A
CSA-C22.2 DC 60 V
1...63 A (1-pole)
No. 235
DC 125 V
1...63 A (2 poles in
series)
UL
UL 489 / AC 240 V
1...63 A
CSA-C22.2 AC 480Y/277 V 1...32 A
No. 5
DC 60 V
1...63 A (1-pole)
DC 125 V
1...63 A (2 poles in
series)
Technical Data
Rupture capacity
to IEC/EN 60947-2 (Ics) AC 7,500 A / DC 10,000 A
to IEC/EN 60947-2
(Icu)
AC/DC 10,000 A
to UL 489
AC/DC 10,000 A
to UL1077
Number of
poles
1-pole
1-pole
2-, 3-,
4-pole
1-pole
2-pole in
series
Un
In
TC
AC 240 V 1...63 A 1
AC 277 V 1...63 A 1
AC 480 V 1...63 A 1
DC 60 V 1...63 A 1
DC 125 V 1...63 A 1
OL SC
1 7.5 kA, U1
0 5 kA, U1
1 5 kA, U1
0 7.5 kA, U1
0 7.5 kA, U1
Insulation coordination
6 kV/3 (reinforced insulation
at operating area)
Degree of protection
IP20
Vibration (sinusoidal)
test to IEC 60068-2-6,
test Fc
± 0.38 mm (10–57 Hz), 5 g
(57–500 Hz)
10 frequency cycles per axis
Shock, test to
IEC 60068-2-27, test Ea
30 g (11 ms)
Corrosion, test to IEC
60068-2-11, test Ka
96 hrs in 5% salt mist
Humidity, test to IEC
60068-2-78, test Cab
48 hours at 95% RH,
temperature +40°C
Terminals
screw terminals
Vertical connection possible
by means of busbars
Tightening torque
2 Nm max.
Cable cross section
≤35 mm²
Ambient temperature:
-35°C...+ 70°C
Mounting
rail mounting
Mass
approx. 116 g per pole (EN 60947-2/
UL 1077) approx. 131 g per pole
(UL 489)
1638
www.e-t-a.de
1