English
Language : 

4130-G211 Datasheet, PDF (1/2 Pages) ETAL Group – Motors, transformers, solenoids, battery chargers, power supplies, appliances, machinery, extra low voltage systems
High Performance Thermal Circuit Breaker 4130-...
Description
Single pole high performance thermal circuit breaker, with push-to-reset
tease free, trip-free snap action mechanism (R-type TO CBE to EN
60934). Designed for threadneck panel mounting and for applications
with a high fault current switching requirement.
Approved to CBE standard EN 60934 (IEC 60934).
US patent number: US 6,040,747
Typical applications
Motors, transformers, solenoids, battery chargers, power supplies,
1
appliances, machinery, extra low voltage systems.
4130-...
Ordering information
Type No.
4130 single pole thermal circuit breaker
Mounting
G2 M12x1, knurled nut (bulk shipped with 5 pcs plus)
G4 M12x1, hex nut and knurled nut (bulk shipped with 5 pcs plus)
Number of poles
1 single pole, thermally protected
Actuator configuration
1 black push button
Terminal design
K4 terminal M6x8
screw and washer bulk shipped
Characteristic curve
M1 medium delay
Current ratings
20... 80 A
4130 - G2 1 1 - K4 M1 - 20 A ordering example
Preferred types
Preferred types Standard current ratings (A)
20 25 30 35 40 45 50 60 70 80
4130-G211-K4M1- x x x x x x x x x
4130-G411-K4M1- x x x x x x x x x
Standard current ratings and typical internal resistance values
Current
rating (A)
20
25
30
35
35
Internal
Current
resistance (Ω) rating (A)
< 0.02
40
< 0.02
50
< 0.02
60
< 0.02
70
< 0,02
80
Internal
resistance (Ω)
< 0.01
< 0.01
< 0.01
< 0.01
< 0,01
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; DC 50 V
Current rating range
20...80 A
Typical life
AC 240 V: 20...70 A
DC 50 V: 20...80 A
Ambient temperature
100 operations at 2 x IN, inductive
500 operations at 2 x IN, resistive
500 operations at 2 x IN, inductive
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
(IEC 60664)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
(reinforced insulation in the mounting area)
Dielectric strength
operating area
test voltage
AC 3,000 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
Interrupting capacity
(UL 1077)
800 A
IN
20...80 A
20...60 A
80 A
20...50 A
60...80 A
UN
AC 240 V
AC 120 V
AC 120 V
DC 50 V
DC 50 V
1,000 A
3,500 A
2,000 A
3,500 A
2,000 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Vibration
8 g (57-500 Hz) ± 0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
25 g (11 ms)
to IEC 60068-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 55 g
Approvals
Authority
VDE
UL
CSA
Standard
Rated voltage
IEC/EN 60934 AC 240 V
DC 50 V
UL 1077
AC 240 V
DC 50 V
C22.2 No 235 AC 240 V
DC 50 V
Current ratings
20 A…70 A
20 A…80 A
20 A…80 A
20 A…80 A
20 A…80 A
20 A…80 A
1646
www.e-t-a.de
1