Thermal-Magnetic Circuit Breakers 3600/3900
Description
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Designed for plug-in mounting with E-T-A sockets
17-P10-Si, 23-P10-Si, 63-P10-Si; or panel mounting using E-T-A clips.
Featuring an unprotected shunt tap terminal and optional auxiliary
contacts. Type 3900 offers lower internal resistance values and is fitted
as standard with auxiliary contacts and an intermediate reset position
in which all contacts are isolated.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Process control systems, instrumentation, communications systems,
rail vehicles.
1
3600
3900
standard type
low-resistance type
Ordering information
Type No.
3600 standard version with shunt tap terminal -3
3900 low-resistance version
Terminal design
P10 blade terminals 6.3-0.8 (QC .250)
Auxiliary contacts (3900: intermediate position as standard)
Si
with blade terminals 6.3-08,one each NO/NC,
Current ratings
0.05...16 A (type 3600)
0.05...10 A (type 3900)
3600 - P10 - Si - 10 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Preferred types
Preferred types
3600-P10-Si-
3900-P10-Si-
Standard current ratings (A)
0.5 1 2 4 8 10 16
x
x
x
x
x
x
x
x
x
x
x
Standard current ratings and typical internal resistance values
Current
ratings
(A)
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
Internal resistance
(Ω)
3600
3900
447
131
40
19.3
10.4
7.1
4.3
2.5
1.67
0.61
0.38
0.24
211
48
12.4
5.4
3.1
2.0
1.32
0.76
0.49
0.21
0.101
0.078
Current
ratings
(A)
3
4
5
6
7
8
10
12
14
15
16
Internal resistance
(Ω)
3600
3900
0.19
0.090
0.061
0.041
0.034
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
0.054
0.035
0.025
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 65 V)
Current rating range
3600: 0.05...16 A
3900: 0.05...10 A
Auxiliary circuit
1 A, AC 240 V / DC 65 V
Typical life
Ambient temperature
5,000 operations at 1 x IN, inductive
5,000 operations at 2 x IN, resistive
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
(IEC 60664 and 60664 A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
main/aux. circuit
aux. circuit 4-5/6-7
test voltage
AC 3,000 V
AC 1,500 V
AC 840 V
Insulation resistance
>100 MΩ (DC 500 V)
Interrupting capacity Icn
3600
0.05...0.8 A
1...2 A
2.5...16 A
3900
0.05...0.2 A
0.3...2 A
2.5...10 A
self-limiting
200 A
400 A
Interrupting capacity
(UL 1077)
IN
0.05...16 A
type 3600: 0.05...16 A
UN
AC 250 V
DC 80 V
1,000 A
1,000 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Vibration
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 45 g
1646
www.e-t-a.de
1