Thermal-Magnetic Circuit Breaker 3500
Description
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Featuring a flange for panel mounting and optional
auxiliary contacts. Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Control systems, instrumentation, medical equipment, machine tools,
robotics, communications systems.
Ordering information
1
3500
Type No.
3500 standard version
Terminal design
P10 blade terminals 6.3-0.8 (QC .250), tinned
Auxiliary contacts (optional)
Si auxiliary contacts, silver plated
terminals one each N/O and N/C
Current ratings
0.05...16 A
3500 - P10 - Si - 10 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Standard current ratings and typical internal resistance values
Current
rating (A)
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
Internal
Current
resistance (Ω) rating (A)
447
3
131
4
40
5
19.3
6
10.4
7
7.1
8
4.3
10
2.5
12
1.67
14
0.61
15
0.38
16
0.24
Internal
resistance (Ω)
0.19
0.090
0.061
0.041
0.034
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
Approvals
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
Current rating range
0.05...16 A
Auxiliary circuit
1 A, AC 240 V / DC 65 V
Typical life
Ambient temperature
5,000 operations at 1 x IN, inductive
5,000 operations at 2 x IN, resistive
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
(IEC 60664 and 60664 A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
main/aux. circuit
aux. circuit 4-5/6-7
test voltage
AC 3,000 V
AC 1,500 V
AC 840 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
0.05...0.8 A self-limiting
1...2 A
200 A
2.5...16 A 400 A
Interrupting capacity
(UL 1077)
IN
0.05...16 A
0.05...16 A
UN
AC 250 V
DC 80 V
1,000 A
1,000 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Vibration
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 40 g
Authority
VDE
UL
CSA
Standard
IEC/EN 60934
UL 1077
C22.2 No 235
C22.2 No 235
Rated voltage
AC 240 V
DC 65 V
AC 250 V
DC 80 V
AC 250 V
DC 80 V
Current ratings
0.05...16 A
0.05...16 A
0.05...16 A
0.05...16 A
0.05...16 A
0.05...16 A
1646