English
Language : 

3200-5A Datasheet, PDF (1/4 Pages) ETAL Group – Control equipment, extra-low voltage wiring systems and components
Thermal-Magnetic Overcurrent Circuit Breaker 3200
Description
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
press-to-reset, snap action mechanism and additional manual release
(M-type TM CBE to EN 60934). Designed for plug-in mounting with E-T-A
sockets 10 and 16.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Control equipment, extra-low voltage wiring systems and components.
Ordering information
1
3200-...
Type No.
3200 plug-in
Current ratings
0.05...25 A
Technical data
3200 - 5 A
ordering example
Standard current ratings and typical internal resistances
Current
rating (A)
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
3
Internal
Current
resistance (Ω) rating (A)
534
4
149
5
56
6
24.2
7
13.6
8
8.1
10
5.25
12
3.55
14
2.02
15
0.90
16
0.51
18
0.36
20
0.23
25
Internal
resistance (Ω)
0.141
0.107
0.060
0.049
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
Approvals
For further details please see chapter: Technical Information
Voltage rating
AC 240 V, 50/60 Hz; DC 28 V
Current ratings
0.05...25 A
Typical life
Ambient temperature
500 operations at 1 x IN, inductive
4,000 operations at 1 x IN, resistive
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
(IEC 60664 and 60664 A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage
AC 3,000 V double insulation
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
0.05...0.8 A
1...2 A
2.5...25 A
self-limiting
200 A
400 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Vibration
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 50 g
Authority Standard
VDE
IEC/EN 60934
Rated voltage
AC 240 V
DC 28 V
Current ratings
0.05...25 A
0.05...25 A
1646
www.e-t-a.de
1