English
Language : 

3130-F Datasheet, PDF (1/6 Pages) ETAL Group – Motors, transformers, solenoids, household and office machines, electrical tools, mobile homes, boating, construction vehicles, medical equipment to EN 60601
Thermal Overcurrent Circuit Breaker 3130
Description
Single, two and three pole rocker switch/thermal trip free circuit breakers
(S-type TO CBE to EN 60934) of compact design for snap-in panel
mounting. Available either with protection on one/both/all poles or,
in the case of the double pole version, protection on one pole only.
Illumination is optional and there is a choice of rocker colours.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Motors, transformers, solenoids, household and office machines, electrical
tools, mobile homes, boating, construction vehicles, medical equipment
1
to EN 60601.
3130
1-pole
3-pole
Standard current ratings and typical internal resistance values
Current Internal resistance Current Internal resistance
rating (A) per pole (Ω)
rating (A) per pole (Ω)
0.1
94
4
0.0435
0.2
24
5
0.0325
0.3
12
6
0.0215
0.4
5.30
7
0.0165
0.5
4.20
8
0.0165
0.8
1.50
10
< 0.02
1
0.9
12
< 0.02
1.2
0.80
14
< 0.02
1.5
0.45
15
< 0.02
2
0.27
16
< 0.02
2.5
0.0785
18
< 0.02
3
0.0595
20
< 0.02
3.5
0.0565
Illumination voltage/power consumption
operating voltage
12 V
24 V
48 V
115 V
230 V
400 V
power consumption
1-pole
2-/3-pole
Y+R
9 mA
2 mA
9 mA
2 mA
9 mA
2 mA
< 1 mA
0.9 mA
< 1 mA
0.9 mA
-
0.9 mA
2-/3-pole
G
3.5 mA
3.5 mA
3.5 mA
2.8 mA
2.8 mA
2.8 mA
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; 3 AC 415 V; DC 50 V
(UL: AC 250 V; 3 AC 250 V; DC 50 V)
Current ratings
0.1...20 A 1-pole
0.1...16 A 2- and 3-pole
Typical life
AC 240 V: 0.1...20 A
DC 50 V: 0.1...4 A
4.5...16 A
DC 28 V: 0.1...20 A
AC 240 V: 0.1...16 A
DC 50 V: 0.1...16 A
3 AC 415 V: 0.1...16 A
Ambient temperature
1-pole
30,000 operations at 1 x IN, inductive
30,000 operations at 1 x IN, inductive
30,000 operations at 1 x IN, resistive
30,000 operations at 1 x IN, inductive
2-pole
50,000 operations at 1 x IN, inductive
50,000 operations at 1 x IN, inductive
3-pole
30,000 operations at 1 x IN, inductive
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
(IEC 60664 and 60664 A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V
current path/current path AC 1,500 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
0.1...2 A
2.5...20 A
2.5...16 A
2.5...12 A
14 + 16 A
10 x IN
150 A
250 A
150 A
130 A
1-pole
2-pole
3-pole
3-pole
Interrupting capacity (UL 1077)
1, 2-pole
IN
0.1...16 A
UN
AC 250 V
Inc
3500 A
3-pole
0.1...12 A 3 AC 250 V
5000 A
1,2-pole
0.1...16 A
DC 50 V
2000 A
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
operating area IP40
terminal area IP00
5 g (57-500 Hz) ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
1-pole: 25 g (11 ms) 2 + 3-pole: 20 g (11 ms)
to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
approx. 45 g (three pole)
approx. 31 g (double pole)
approx. 17 g (single pole)
1646
www.e-t-a.de
1