English
Language : 

2216-S1 Datasheet, PDF (1/8 Pages) ETAL Group – Protection of AC and DC control circuits in industrial automation applications and buildings, e.g. in the chemical industry, power plants, steel industry and machine construction
Thermal-Magnetic Circuit Breaker 2216-S…
Description
One and two pole thermal-magnetic circuit breaker in compact design
with slide actuator, trip-free mechanism, various trip characteristics and
optional auxiliary contacts.
Meets the requirements of the circuit breaker standard EN 60934
(IEC 60934): S-type, TM.
2216-S11
Typical applications
Protection of AC and DC control circuits in industrial automation
applications and buildings, e.g. in the chemical industry, power
plants, steel industry and machine construction (machine tools,
packing machines etc.)
with socket
80plus
1
with socket
81plus
Ordering information
Type no.
2216 thermal-magnetic circuit breaker
Mounting method
S1 plug-in mounting
Number of poles
1 1-pole
2 2-pole
Additional function / accessories
0 without
Main terminals
P1 blade terminals A6.3 x 0.8 with polarising
tooth (standard)
Characteristic curve
F1 therm. 1.01-1.4 x IN; magn. 2-4 x IN (only for DC)
F2 therm. 1.01-1.4 x IN; magn. 3-6 x IN AC / 4-8 IN DC
M1 therm. 1.01-1.4 x IN; magn. 6-12 x IN AC / 8-15 IN DC
Auxiliary contacts
S0 without auxiliary contact
S1 with auxiliary contact
Auxiliary contact function
0 without
1 change-over
Auxiliary contact terminals
0 without
1 blade terminals A6.3 x 0.8
with polarising tooth (standard)
Voltage rating
A ≤ AC 277 V, ≤ DC 80 V
Current ratings
0.5....16 A
2216 - S1 1 0 - P1 F1- S1 1 1 - A-16A Ordering example
Standard current ratings and typical internal resistance values
Current rating Internal
Current rating Internal
(A)
resistance (Ω) (A)
resistance (Ω)
0.5
5.0
6
1
1.1
8
2
0.3
10
3
0.14
12
4
0.09
15
5
0.06
16
0.05
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
Technical data
Voltage rating
Current rating range
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664)
Dielectric strength
operating area
main/aux. circuit
Open aux. circuit
Insulation resistance
Interrupting capacity Icn
Interrupting capacity
(UL 1077)
Degree of protection
(IEC 60529)
Vibration
curve F1:
curves F2, M1:
Shock
curve F1:
curves F2, M1:
Corrosion
Humidity
Mass
AC 240 V (50/60 Hz); DC 50 V (1-pole)
DC 80 V (2-pole)
0.5...16 A
AC 240 V, 0.5 A (VDE)
AC 277 V, 0.5 A (UL)
DC 50 V, 1 A (VDE/UL)
6,000 operations at 1 x IN
3,000 operations at 1 x IN
DC 80 V, 2-pole
-30...60 °C
2,5 kV/2
re-inforced insulation in operating area
test voltage AC 3,000 V
test voltage AC 1,500 V
AC 1,000 V
> 100 MΩ (DC 500 V)
AC 240 V 1-pole
DC 32 V 1-pole
DC 50 V 1-pole
AC 240 V 2-pole
DC 32 V 2-pole
DC 80 V 2-pole
300 A
1500 A
600 A
400 A
1500 A
600 A
AC 277 V
DC 50 V 1-pole
DC 80 V 2-pole
1,000 A
1,000 A
1,000 A
operating area IP30
terminal area IP00
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz);
8 g (57-500 Hz) ± 0.61 mm (10-57 Hz)
test to IEC 60068-2-6, test Fc,
10 frequency cycles per axis
15 g (11 ms) for shock direction 1-6
30 g (11 ms) for shock direction 1-6
test to IEC 60068-2-27, test Ea
96 hrs in 5 % salt mist,
test to IEC 60068-2-11, test Ka
240 hrs in 95 % RH,
test to IEC 60068-2-78, test Cab
approx. 25 g (per pole with aux. contact)
1646
www.e-t-a.de
1