English
Language : 

2210-S2 Datasheet, PDF (1/6 Pages) ETAL Group – Process control equipment, robotics, machine tool control, communicationssystems, instrumentation, rail vehicles. Special versions, e.g. for aggressive environmental conditions and low voltages (e. g. 5 V) on request
Thermal-Magnetic Circuit Breaker 2210-S2...
Description
One, two and three pole thermal-magnetic circuit breakers with tripf­ree
mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC
934). Designed for panel or plug-in mounting. Available with auxiliary
contacts (1 x N/O, 1 x N/C) for status signalling. Two and three pole
models are internally linked to ensure that both/all poles trip in the
event of an overload on one pole, even if the actuator is held in the ON
position. A choice of characteristic curves further extends the range
of applications possibilities for these CBEs. Special auxiliary contact
versions for industrial atmosphere and low voltages (e. g. 5 V) available
on request.
Approved to CBE standard EN 60934 (IEC 60934).
Suitable for use in distribution rails – see section Power Distribution
Systems.
1
Typical applications
2210-S2..
Process control equipment, robotics, machine tool control, communications
systems, instrumentation, rail vehicles. Special versions, e.g. for aggressive
environmental conditions and low voltages (e. g. 5 V) on request.
Standard current ratings and typical internal resistance values
Current
rating (A)
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
3
4
5
6
8
10
12
16
20
25
Internal resistance (Ω)
F1
F2
M1
T1
M3
fast acting
for DC only
162
39.3
17.5
9.2
6.8
4.2
2.8
1.6
0.78
0.42
0.26
0.18
0.12
0.092
0.054
0.025
0.022
≤ 0.02
≤ 0.02
-
-
fast acting
delay
for AC+DC
162
39.3
17.5
9.2
6.8
4.2
2.8
1.6
0.78
0.42
0.26
0.18
0.12
0.092
0.054
0.025
0.02
≤ 0.02
≤ 0.02
-
-
standard
for AC+DC
92
26.1
11.6
6.6
4.1
3
1.65
1.10
0.47
0.28
0.183
0.124
0.077
0.063
0.045
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
delayed
low
resistance
only for AC
81
24.2
10.4
6.0
3.9
2.7
1.53
0.98
0.42
0.24
0.17
0.12
0.073
0.055
0.039
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
standard
delay
42
11.7
5.6
2.9
1.75
1.42
0.75
0.5
0.22
0.136
0.083
0.057
0.041
0.032
0.021
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
-
-
Preferred types
Preferred types
Standard current ratings (A)
1-pole:
1 2 4 6 8 10 16
2210-S211-P1F1-H111- x x x x x
2210-S211-P1M1-H111- x x x x x x x
2210-S211-P1M1-Z111- x x x x x x x
2-pole:
2210-S221-P1M1-H111- x x x x x x x
2210-S221-P1M1-H211- x x x x x x x
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 250 V*; 3 AC 433 V (50-60Hz); DC 65 V
(*UL: AC 277/480 V; DC 65 V)
Current rating range
0.1...25 A for curves M1, T1
0.1...16 A for curves F1, F2, M3
Auxiliary circuit
1 A, AC 240 V/DC 65 V, resistive
Typical life
Ambient temperature
10,000 operations at 1 x IN, inductive
-30...+60 °C (-22...+140 °F) T 60
Insulation co-ordination
(IEC 60664 and 60664A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V
main/aux. circuit
AC 1,500 V
aux. circuit 11-12/23-24 AC 1,000 V
pole/pole
AC 1,500 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
curves F1, F2, M1, T1:
curve M3:
0.1...5 A 400 A
6...25 A
800 A
0.1...16 A 2,500A
0.1...2 A AC 200 A
(at DC 32 V)
DC 400 A
Interrupting capacity (UL 1077)
IN
AC 277 V 1-pole
0.1...16 A
5,000 A
20...25 A
2,000 A
AC 277/480 V 2-/3-pole
5,000 A
2,000 A
DC 65 V
2,000 A
2,000 A
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
operating area IP30
terminal area IP00
curves F1, F2:
3 g (57-500 Hz), ± 0.23 mm (10-57 Hz)
curves M1, M3, T1:
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
curves F1, F2:
25 g (11 ms), directions 1, 2, 3, 4, 5
10 g (11 ms), direction 6
curves M1, M3, T1:
25 g (11 ms), directions 1, 2, 3, 4, 5
20 g (11 ms), direction 6
to IEC 60068-2-27, test Ea
96 hours in 5 % salt mist
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 50 g per pole
1646
www.e-t-a.de
1