English
Language : 

2-6500 Datasheet, PDF (1/2 Pages) ETAL Group – Motors, transformers, extra low voltage wiring
Motor Protection Control 2-6500-...
Description
Bimetal operated single pole motor protection control with automatic
reset actuation, small physical size, reliable snap-action mechanism.
Caution: In specifying this product, care should be taken to ensure that
automatic motor re-start does not represent a safety hazard.
Typical applications
Motors, transformers, extra low voltage wiring.
Ordering information
1
2-6500-...
Type No.
2-6500 surface type with flange
Terminal design
P10 blade terminals 6.3-0.8 (QC .250)
Shunt terminal (optional)
A3 blade terminals or solder terminals; max. load 5 A
Current ratings
0.1...10 A
2-6500 - P10 - ... - 6 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Standard current ratings and typical internal resistance values
Current
rating (A)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
1.2
1.5
1.8
Internal
Current
resistance (Ω) rating (A)
140
2
47.5
2.5
20.5
3
11.4
3.5
7.25
4
5.35
4.5
3.8
5
2.95
6
1.92
7
1.32
8
0.85
9
0.59
10
Internal
resistance (Ω)
0.47
0.33
0.212
0.155
0.107
0.095
0.072
0.054
0.032
0.02
< 0.02
< 0.02
Technical data
Voltage rating
Current ratings
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A)
Dielectric strength
(IEC 60664 and 60664A)
Insulation resistance
Interrupting capacity
Reset time at 23 °C
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
AC 250 V (50/60 Hz); DC 28 V
0.1...10 A (up to 15 A upon request)
100,000 operations at 2 x IN
Protection is ensured for 18 days of
continuous locked rotor condition with
Ik ≤ 6 x IN, max. 30 A
(unsupervised duty)
-10...+60 °C (-10...+140 °F)
rated impulse
pollution
withstand voltage degree
2.5 kV
3
test voltage AC 2,000 V
> 100 MΩ (DC 500 V)
8 x IN (co-co-co)
≥ 30 sec
≤ 70 sec
housing IP30
terminal area IP00
5 g (57-500 Hz) ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
15 g (11 ms)
test to IEC 60068-2-27, test Ea
48 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 20 g
Approvals
Authority
UL
CSA
Standard
UL 1077
C22.2 No 235
Rated voltage
AC 250 V
DC 28 V
AC 250 V
DC 28 V
Current ratings
0.1 A…15 A
0.1 A…15 A
0.1 A…15 A
0.1 A…15 A
1646
www.e-t-a.de
1