English
Language : 

1410-L110-L1F1 Datasheet, PDF (1/2 Pages) ETAL Group – Motors, transformers, solenoids, PCBs, hand-held machines, appliances, instrumentation
Thermal Overcurrent Circuit Breaker 1410-L1
Description
Single pole press-to-reset thermal circuit breaker with extremely fast
overload switching performance (R-type TO CBE to EN 60934).
Miniaturised construction minimises PCB real estate required.
PCB mounting or integral mounting. Largely temperature-insensitive.
Typical applications
Motors, transformers, solenoids, PCBs, hand-held machines, appliances,
instrumentation.
Ordering information
1
1410-L1...
Type No.
1410 single pole circuit breaker
Configuration
L integral mounting or PCB mounting
Mounting
1 footprint 16.3x4.6
Number of poles
1 1-pole, thermally protected
Hardware
0 without
Terminal design
L1 solder pins 1.8x0.8 silver-plated
Characteristic curve
F1 fast acting
Actuator, Type and Colour
S01 reset button, black
Current ratings
0.63...10 A
1410 - L 1 1 0 - L1 F1 - S01 - 0.8 A ordering example
*mounting hardware bulk shipped
Preferred types
Preferred types
1410-L110-L1F1-
S01-
Standard current ratings (A)
0.63 0.8 1 1.5 2 2.5 3.15 4 5 6.3 8 10
x x x x x x x xx x x x
Standard current ratings and typical internal resistance values
Current
rating (A)
0.63
0.8
1
1.5
1.8
2
2.5
Internal
Current
resistance (Ω) rating (A)
1.8
3.15
1.7
4
1.3
5
<1
6.3
<1
8
<1
10
< 0.15
Internal
resistance (Ω)
< 0.12
< 0.1
< 0.1
< 0.1
< 0.1
< 0.1
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; DC 28 V
(UL: AC 250 V; DC 50 V)
Current rating range 1-2 0.63...10 A
Typical life
AC 240 V: 0.63...2.25 A 500 break operations at 2 x IN, inductive
2.5...10 A 500 break operations at 2 x IN, resistive
DC 50 V: 0.63...2.25 A 500 break operations at 2 x IN, inductive
DC 28 V: 2.5...10 A 500 break operations at 2 x IN, inductive
Ambient temperature
-20...+70 °C (-4...+158 °F)
Insulation co-ordination
(IEC 60664 and 60664 A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage
AC 1,500 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
(o-o-o)
Interrupting capacity
(UL 1077)
0.63...2 A
2.5...8 A
10 A
3.15...10 A
0.63...10 A
0.63...10 A
12 x IN
8 x IN, AC max. 50 A
6 x IN, AC
10 x IN, DC
2,000 A AC 250 V
200 A DC 50 V
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Vibration
8 g (57-500 Hz) ± 0.61 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Shock
20 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion
48 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
96 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 5 g
Approvals
Authority
VDE
UL
CSA
Standard
IEC/EN 60934
UL 1077
C22.2 No 235
Rated voltage
AC 240 V
DC 50 V
DC 28 V
AC 250 V
DC 50 V
AC 125 V
DC 48 V
Current ratings
0.63 A…6,3 A
0.63 A…2.25 A
2.5 A…10 A
0.63 A…10 A
0.63 A…10 A
0.63 A…8 A
0.63 A…8 A
1651
www.e-t-a.de
1