English
Language : 

1140-E211-P1M1 Datasheet, PDF (1/2 Pages) ETAL Group – Motors, transformers, solenoids, hand-held machines and appliances
Thermal Overcurrent Circuit Breaker 1140-...
Description
Miniaturised single pole thermal circuit breaker with push-to-reset
tease-­free, trip-free, snap action mechanism (R-type TO CBE to EN
60934). Available in versions for panel mounting, snap-in or threadneck,
or as an integral type. For lower current ratings see types 104, 105, 106.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Motors, transformers, solenoids, hand-held machines and appliances.
Ordering information
1140-E...
1
1140-F...
1140-G.1.
Type No.
1140 single pole thermal circuit breaker
Mounting
E2 integral mounting
F1 snap-in panel mounting
G1 threadneck panel mounting 3/8-27UNS with hex nut and
knurled nut (hardware bulk shipped with 5 pcs plus)
Number of poles
1 1-pole protected
Actuator style
1 black push button
Terminal design
P1 blade terminals A6.3-0.8 (QC .250)
Characteristic curve
M1 medium delaye
Current ratings
3.5...16 A
1140 - F1 1 1 - P1 M1 - 10 A = ordering example
Preferred types
Preferred types Standard current ratings (A)
4 5 6 7 8 9 10 11 12 13 14 15 16
1140-G111-P1M1- x x x x x x x x x x x x x
Standard current ratings and typical internal resistance values
Current
rating (A)
3.5
4
5
Internal
Current
resistance (Ω) rating (A)
0.06
10
0.04
11
0.03
12
Internal
resistance (Ω)
< 0.02
< 0.02
< 0.02
Technical data
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; DC 48 V
(UL: AC 250 V; DC 50 V)
Current ratings
3.5...16 A
Typical life
AC + DC
3.5...8 A
9...16 A
Ambient temperature
200 operations at 2 x IN, inductive
100 operations at 2 x IN, inductive
-20...+60 °C (-4...+140 °F) T 60
Insulation co-ordination
(IEC 60664 and 60664 A)
rated impulse
pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage
AC 3,000 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn 3.5...8 A 8 x IN
9...16 A 120 A
Interrupting capacity
(UL 10777)
IN
3.5...16 A
3.5...16 A
UN
DC 50 V
AC 250 V
2,000 A
2,000 A
Degree of protection
operating area IP40
(IEC 60529/DIN 40 050) terminal area IP00
Vibration
10 g (57-500 Hz) ± 0.76 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Shock
25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 10 g
6
0.02
13
< 0.02
7
< 0.02
14
< 0.02
Approvals
8
< 0.02
15
< 0.02
Authority Standard
Rated voltage Current ratings
9
< 0.02
16
< 0.02
VDE
IEC/EN 60934 AC 240 V
3.5 A…16 A
DC 48 V
3.5 A…16 A
UL
UL 1077
AC 250 V
3.5 A…16 A
DC 50 V
3.5 A…16 A
CSA
C22.2 No 235 AC 250 V
DC 50 V
3.5 A…15 A
3.5 A…16 A
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
1635
www.e-t-a.de
1