English
Language : 

1115-F111-P1T1 Datasheet, PDF (1/2 Pages) ETAL Group – Single pole thermal reset circuit breaker
Thermal Circuit Breaker 1115-...
Description
Single pole thermal reset circuit breaker
l Space-saving, slim design
l Ease of installation through snap-in frame
l Reliable, trip-free mechanism
l Approvals: UL1077, EN60934
l Attractively low price
Typical applications
Power supply units, UPS equipment, battery chargers, oxygen treat-
ment devices, office machines
1
Order numbering code
1115
Type No.
1115 single pole thermal circuit breaker
Mounting method
F1 snap-in mounting
Number of poles
1 1 pole, thermally protected
Accessories, style
1 black push button
Terminals
P1 blade terminals A 6.3 x 0.8 mm
Characteristic curve
T1 thermal 3...16 A
T2 thermal 1...2.5 A
Current ratings
1...16A
1115 - F1 1 1 -P1 T1 - 10 A ordering example
Approvals
Technical Data
Rated voltage
Current rating range
Typical life
Rupture capacity
UL1077
EN 60934
Ambient temperature
Vibration
Shock
Mass
AC 250 V; DC 32 V
1...16 A
500 operations at 1.5 times rated
current, resistive load, AC 125 V
50 operations at 2 times rated
current, inductive load, AC 250 V
1.000 A (C, 1), AC 250 V
200 A (C, 1), DC 32 V
500 A (INC1), AC 250 V
-20°C … + 60°C
57 Hz acceleration 30m/s2 (3g)
in X, Y, Z directions (twice/min.)
300m/s2 (30g) in X, Y, Z directions
approx. 8g
Approval
authority
Standard
UL
UL1077
(E67320)
TÜV
EN 60934/
IEC 60934
Rated
voltage
AC 250 V
DC 32 V
AC 250 V
Current
rating
range
1...16 A
1...16 A
Approval
mark
Cut-out dimensions
13,8 + 0,2
–0
Ø
15,8
+
0,2
–0
Current ratings and typical voltage drop
Current rating Voltage drop
range (A)
(mV)
1
< 1000
1,5
< 500
2
< 500
2,5
< 500
3
< 250
3,5
< 250
4
< 250
5
< 250
6
< 250
7
< 250
Current rating Voltage drop
range (A)
(mV)
8
< 250
9
< 250
10
< 250
11
< 250
12
< 250
13
< 250
14
< 250
15
< 250
16
< 250
1646
www.e-t-a.de
1