English
Language : 

1110-F112-P1M1 Datasheet, PDF (1/2 Pages) ETAL Group – Motors, transformers, solenoids, extra low voltage systems, household and office machines, instrumentation, marine applications, mobile homes
Thermal Overcurrent Circuit Breaker 1110-...
Description
Tease-free, trip-free, snap action mechanism. Designed for snap-in
panel mounting utilising round hole or industry standard fuse-holder
cut-out dimensions. Featuring an ergonomically styled two colour
actuator with indicator band clearly showing the tripped/OFF position.
Approved to CBE standard EN 60934 (IEC 60934): S-type TO CBE
Typical applications
Motors, transformers, solenoids, extra low voltage systems, household
and office machines, instrumentation, marine applications, mobile homes.
1
Ordering information
1110-F1..
Type No.
1110 snap in panel mounting
Mounting
F1 panel thickness 0.8...1.6 mm (.031 -.063 in)
F2 panel thickness 1.8...3 mm (.071-.118 in)
Number of poles
1 1-pole protected
Actuator style
2 black push button/white indicator ring,
push-push function
Terminal design
P1 blade terminals A6.3-0.8 (QC .250)
Characteristic curve
M1 medium delay
Current ratings
0.05...16A
1110 - F1 1 2 - P1 M1 - 0.05 A = ordering example
Preferred types
Preferred types
1110-F112-P1M1-
1110-F212-P1M1-
Standard current ratings (A)
1 1.5 2 3 3.5 4 5 6 7
xxxxxxxxx
xxxx
xx
8 10 15 16
xxxx
xxx
Standard current ratings and typical internal resistance values
Current
rating (A)
0.05
0.08
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
1.2
1.5
1.8
Internal
Current
resistance (Ω) rating (A)
442
2
173
2.5
110
3
27.8
3.5
12.4
4
7.0
5
4.5
6
3.1
7
2.3
8
1.7
10
1.1
12
0.71
15
0.41
16
0.38
Internal
resistance (Ω)
0.25
0.19
0.12
0.09
0.07
0.05
0.04
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
Technical data
For further details please see chapter: Technical Information
Voltage rating
Current rating
AC 250 V; DC 50 V
0.05...16 A
Typical life
IN
operations
Un
I
0.05...10 A
10,000
AC 250 V
1xIN
0.05...10 A
10,000
DC 28 V
1xIN
0.05...10 A
6,000
DC 50 V
1xIN
12...16 A
2,000
DC 50 V
1xIN
Ambient temperature
-20...+60 °C (-4...+140 °F)
Insulation co-ordination rated impulse
pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A)
operating area
test voltage
AC 3,000 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn AC 250 V:
DC 50 V:
DC 28 V:
0,05...10 A 8 x IN
0,05...6.5 A 10 x IN
7...16 A 130 A
7...10 A 200 A
Interrupting capacity
(UL 1077/EN60934 PC 1)
IN
0.05...6 A
7...16 A
0.05...16 A
UN
AC 250 V
AC 125 V
DC 50 V
1,000 A
1,000 A
1,000 A
Degree of protection
(IEC 60529/DIN 40050)
operating area IP40
terminal area IP00
Vibration
8 g (57-500 Hz) ± 0.61 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Shock
30 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass
approx. 12 g
Approvals
Authority
VDE
UL
CSA
Standard
IEC/EN 60934
UL 1077
C22.2 No 235
C22.2 No 235
Rated voltage
AC 250 V
DC 50 V
AC 250 V
AC 120 V
DC 50 V
AC 250 V
DC 50 V
Current ratings
0.05 A…10 A
0.05 A…16 A
0.05 A…6.6 A
7 A…16 A
0.05 A…16 A
0.05 A…16 A
0.05 A…16 A
1646
www.e-t-a.de
1