English
Language : 

PKY4716PI Datasheet, PDF (5/20 Pages) Ericsson – DC/DC converters, Input 36-75 V, Output up to 25 A/700 W
E
Ericsson Internal
PRODUCT SPECIFICATION
Prepared (also subject responsible if other)
No.
ESECZHW
2/1301-BMR 638T/1eUcehnnical Specification
Approved
SPEKCY/D4(0J0ul0iaPYIosu)eries
Checked
Date
ECHWANG 2008-10-9
Rev
Reference
ECN/LZT 146 380 R2B March 2011
DC/DC converters, Input 36-75 V, Output up to 25 A/700 W © Ericsson Power Modules AB
2 (10)
5
28V, 21.5A/600W Electrical Specification
PKY 4616 PI
TP1 = -40 to +100ºC, VI = 36 to 75 V, sense pins connected to output pins unless otherwise specified under Conditions.
Typical values given at: TP1 = +25°C, VI= 53 VI max IO, unless otherwise specified under Conditions.
Additional Cin = 220 µF.See Operating Information section for selection of capacitor types.
Characteristics
Conditions
min
typ
max
Unit
VI
Input voltage range
36
75
V
VIoff
Turn-off input voltage
Decreasing input voltage
32.1
33
34.5
V
VIon
Turn-on input voltage
Increasing input voltage
33.3
35
35.5
V
CI
Internal input capacitance
35.2
μF
PO
Output power
0
600
W
50 % of max IO
95
η
Efficiency
max IO
93.5
94.5
%
50 % of max IO, VI = 48 V
95
max IO, VI = 48 V
93.5
94,5
Pd
Power Dissipation
max IO
34.9
41.7
W
Pli
Input idling power
IO = 0 A, VI = 53 V
5.7
17
W
PRC
Input standby power
VI = 53 V (turned off with RC)
0.2
0.3
W
fs
Switching frequency
0-100 % of max IO
145
150
155
kHz
VIOVP Input over voltage protection
0-100 % of max IO
80
83
86
V
VOi
VO
Vtr
ttr
tr
ts
tf
tRC
IO
Ilim
Isc
Cout
VOac
OVP
Vaux
Iaux
Output voltage initial setting and
accuracy
Output adjust range
Output voltage tolerance band
Idling voltage
Line regulation
Load regulation
Load transient
voltage deviation
Load transient recovery time
Ramp-up time
(from 10−90 % of VOi)
Start-up time
(from VI connection to 90 % of VOi)
VI shut-down fall time
(from VI off to 10 % of VO)
RC start-up time
RC shut-down fall time
(from RC off to 10 % of VO)
Output current
Current limit threshold
Short circuit current
Recommended Capacitive Load
Output ripple & noise
Over voltage protection
Auxiliary output voltage
Auxiliary output current
TP1 = +25°C, VI = 53 V, IO = 21.5 A
See operating information
10-100 % of max IO
IO = 0 A
max IO
VI = 53 V, 1-100 % of max IO
VI = 53 V, Load step 25-75-25 % of
max IO, di/dt = 1 A/μs
10-100 % of max IO
max IO
IO = 0 A
max IO
max IO
IO = 0 A
TP1 < max TP1
TP1 = 25ºC, see Note 1
TP1 = 25ºC
See ripple & noise section,
max IO, VOi
TP1 = +25°C, VI = 53 V, 0-100 % of
max IO
TP1 = +25°C, VI = 53 V, 0-100 % of
max IO
max IO, VI = 36-75 V
Note 1:See Operating Information section.
27.72
15.0
27.58
27.44
0
22
0
36.6
8
0
28.0
20
20
±800
40
10
17
0.06
2.7
15
0.06
2.7
27
27.5
180
39
10
28.28
32.0
28.42
28.56
80
80
20
20
21.5
33.5
34
TBD
250
41.4
12
0.05
V
V
V
V
mV
mV
mV
µs
ms
ms
ms
s
ms
ms
s
A
A
A
µF
mVp-p
V
V
A