English
Language : 

B84143-B-R110 Datasheet, PDF (3/10 Pages) EPCOS – 3-Line Filters for Converters and Power Electronics
3-Line Filters
for Converters and Power Electronics
B84143-B*-R110
B84143-B*-R112
Technical data
Rated voltage VR
Rated current I R
Test voltage VP
Overload capability
Leakage current I leak
Climatic category
480/275 V~, 50/60 Hz (type -R110)
520/300 V~, 50/60 Hz (type -R112)
Referred to 40 °C ambient temperature
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
1,5 · IR for 3 min per hour or
2,5 · IR for 30 s per hour
at 480 V~, 50 Hz
25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
IR
Terminal cross section
line side:
load side:
terminal blocks litz wires
A
mm2
mm2
84
1,5
16 4
2,5
25 6
4
36 6
6
50 16
10
66 25
16
90 25
25
120 50
35
150 50
35
200 95
70
I leak
typ1)
mA
< 14
< 14
< 14
< 14
< 14
< 14
< 14
< 14
< 14
< 14
Rtyp
mΩ
26
13
10
6,5
4,3
2,7
2,0
1,4
0,9
0,5
Approx. Ordering code
weight
kg
1,5
B84143-B8-R110
1,5
B84143-B16-R110
2,7
B84143-B25-R11*
3,2
B84143-B36-R11*
3,7
B84143-B50-R11*
4,3
B84143-B66-R11*
7,7
B84143-B90-R11*
8,3
B84143-B120-R11*
9,7
B84143-B150-R11*
13,5
B84143-B200-R11*
Compilation of ordering code
Replace the asterisk * by the code number for the required version:
0 = 480 / 275 V
2 = 520 / 300 V
1) At rated operation
248 03/01