English
Language : 

B44066R6004E230 Datasheet, PDF (3/5 Pages) EPCOS – Power Factor Controller BR604
Power Capacitor
Power Factor Controller Series BR604
Preliminary data
Protection class
- Front plate
- Rear side
Operation
- Supply voltage
- Target cos phi
- Switching and discharge time range
- Number of control series
- Control modes
Measurement
- Measurement voltage range
- Fundamental frequency
- Measurement current (CT)
- Minimum operating current
- Maximum current
- Zero voltage release
Switching outputs
Relay outputs
- Number of relays
- Switching voltage/power
- Expected mechanical life
- Expected electrical life
Ordering Code
Accessories
B44066R6004E230
IP54 according to IEC60529 / DIN 40050
IP20 according to IEC60529 / DIN 40050
230 VAC, 50 and 60 Hz power lines
0.8 ind. – 0.8 cap.
1 – 255 seconds
23 series preset
Series switching (LIFO),
circular switching (FIFO),
self-optimized intelligent control mode
= supply voltage: 230 VAC (L-N)
50 and 60 Hz
x/1 and x/5 Ampere possible
40 mA
5.3 (sinusodial)
< 15 ms
4 steps available
max. 250 VAC, max. 1000 W
> 30 x 106 switching operations
> 5 x 106 switching operations
(load = 200 VA, cosphi = 0.4)
B44066R6004E230
FK PC PM PFC
Page 3 of 5
September 2006