English
Language : 

B88069X2641S102 Datasheet, PDF (2/4 Pages) EPCOS – 2-electrode arrester
Surge arrester
2-electrode arrester
B88069X2641xxxx a)
EF800X
Features
ƒ Standard size
ƒ High follow current capability
ƒ Very fast response time
ƒ Stable performance over life
ƒ Very low capacitance
ƒ High insulation resistance
ƒ RoHS-compatible
Applications
ƒ Application with high follow current
ƒ Power supply
Electrical specifications
DC spark-over voltage 1) 2)
Impulse spark-over voltage
at 100 V/µs - for 99 % of measured values
- typical values of distribution
at 1 kV/µs - for 99 % of measured values
- typical values of distribution
Service life
10 operations
1 operation
10 operations
1 operation
50 Hz, 1 s
50 Hz, 0.18 s (9 cycles)
8/20 µs
8/20 µs
Max. follow current during one voltage half cycle at 50 Hz
Insulation resistance at 100 Vdc
Capacitance at 1 MHz
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
Weight
Operation and storage temperature
Climatic category (IEC 60068-1)
Marking, red positive
a) xxxx = S102 (100 pcs on 5 stripes)
= T502 (500 pcs on tape and reel)
1) At delivery AQL 0.65 level II, DIN ISO 2859
2) In ionized mode
Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845
KB AB E / KB AB PM
Please read Cautions and warnings and
Important notes at the end of this document.
Page 2 of 4
680 ... 1000
V
< 1200
V
< 1000
V
< 1300
V
< 1100
V
5
A
65
A
5
kA
10
kA
200
A
> 10
GΩ
< 1.5
pF
~ 22
V
< 0.5
A
~ 140
V
~ 1.5
g
-40 ... +90
°C
40/ 90/ 21
EF 800 YY O
EF
- Series
800 - Nominal voltage
YY
- Year of production
O
- Non radioactive
Issue 03 / 2008-01-18