English
Language : 

B84143-V6-R27 Datasheet, PDF (2/5 Pages) EPCOS – 3-Line Filters Sine-Wave Output Filters
3-Line Filters
Sine-Wave Output Filters
Technical data
Rated voltage VR
Rated current I R
Test voltage VP
Overload capability
Converter output frequency fM
Converter pulse frequency fP
Voltage drop (input to output) ∆V
Power dissipation PV
Capacitive reactive current Iq
Climatic category
B84143-V*-R27
440/250 V~, 50/60 Hz
referred to 40 °C ambient temperature
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
1,5 · IR for 1 min per hour
0 … 100 Hz
6 … 16 kHz
at I R, 50 Hz
typical value
at 230 V, 50 Hz (typical value)
25/1005/21 (– 25 °C/+ 100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
IR
Terminal
Iq
∆V
PV
Rtyp
Approx. Ordering code
cross section
weight
A
mm2
A
V
W
mΩ
kg
6
4
0,24
10
29
200
5,2
B84143-V6-R27
12
4
0,48
8
37
66
7,9
B84143-V12-R27
16
4
0,81
8
49
49
8,3
B84143-V16-R27
25
6
1,20
7
65
27
11,1
B84143-V25-R27
35
6
1,60
7
70
15
16,6
B84143-V35-R27
270 03/01