English
Language : 

B84143-A6-R206 Datasheet, PDF (2/6 Pages) EPCOS – 3-Line Filters for Converters and Power Electronics
3-Line Filters
for Converters and Power Electronics
Typical circuit diagram
LINE
L1
L2
L3
B84143-A*-R206
LOAD
L1’
L2’
L3’
Technical data
Rated voltage VR
Rated current IR
Test voltage VP
Overload capability
Leakage current I leak
Climatic category
SSB1664-T
480/275 V~, 50/60 Hz
Referred to 40 °C ambient temperature
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
1,5 · IR for 3 min per hour or
2,5 · IR for 30 s per hour
at 480 V~, 50 Hz
25/100/21 (– 25 °C/100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
IR
Terminal
I leak
cross section
A
mm2
mA
6
2,5
< 3,5
12
2,5
< 3,5
25
4
<6
Rtyp
mΩ
72
21
8,5
Approx.
weight
kg
0,8
1,5
2,3
Ordering code
B84143-A6-R206
B84143-A12-R206
B84143-A25-R206
229 03/01