English
Language : 

A71-H10XG Datasheet, PDF (1/2 Pages) EPCOS – 2-Electrode-Arrester
Surge Arrester
2-Electrode-Arrester
A71-H10XG
Ordering code: B88069X3880T502
DC spark-over voltage 1) 2)
Impulse spark-over voltage
at 100 V/µs - for 99 % of measured values
- typical values of distribution
at 1 kV/µs - for 99 % of measured values
- typical values of distribution
Nominal impulse discharge current (wave 8/20 µs)
Single impulse discharge current (wave 8/20 µs)
Nominal alternating discharge current (50 Hz, 1 s)
Alternating discharge current (50 Hz, 9 cycles)
Insulation resistance at 100 Vdc
Capacitance at 1 MHz
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
Weight
Operation and storage temperature
Climatic category (IEC 60068-1)
Marking, green
1) At delivery AQL 0.1 level II and AQL 0.65 level II at 1000 V ±10 %;
DIN ISO 2859
2) In ionized mode
Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845
1000
V
± 15
%
< 1300
V
< 1200
V
< 1400
V
< 1300
V
10
kA
10
kA
10
A
65
A
> 10
GΩ
<1
pF
~ 20
V
~1
A
~ 180
V
~ 1.5
g
-40 ... +90
°C
40/ 90/ 21
1000
YY
O
1000 YY O
- Nominal voltage
- Year of production
- Non radioactive
AB E / AB PM
Page 1 of 2