Surge Arrester
2-Electrode-Arrester
Preliminary data
DC spark-over voltage 1) 2)
Impulse spark-over voltage
at 100 V/µs - for 99 % of measured values
- typical values of distribution
at 1 kV/µs - for 99 % of measured values
- typical values of distribution
Nominal impulse discharge current (wave 8/20 µs)
Single impulse discharge current (wave 8/20 µs)
Nominal alternating discharge current (50 Hz, 1 s)
Alternating discharge current (50 Hz, 9 cycles)
Insulation resistance at 100 Vdc
Capacitance at 1 MHz
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
Weight
Storage temperature
Climatic category (IEC 60068-1)
Marking, red
1) At delivery AQL 0.65 level II, DIN ISO 2859
2) In ionized mode
Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845
A61-A230XF
Ordering code: T. B. D.
230
V
± 20
%
< 500
V
< 450
V
< 800
V
< 700
V
10
kA
12
kA
10
A
> 40
A
> 10
GΩ
< 1.5
pF
< 20
V
< 0.5
A
~ 60
V
~ 1.5
g
-40 ... +90
°C
40/ 90/ 21
230 YY O
230 - Nominal voltage
YY
- Year of production
O
- Non radioactive
AB E / AB PM
Page 1 of 2
Issue 03, 04.04.2002