English
Language : 

LPS41_09 Datasheet, PDF (2/3 Pages) Emerson Network Power – Universal input
Embedded Power for
Business-Critical Continuity
Environmental Specifications
Operating temperature: 0° to 50 °C ambient. Derate each output 2.5% per degree from 50° to 70 °C, -20 °C start up.
Storage temperature: -40 °C to +85 °C
Temperature coefficient: ± 0.4% per °C
Electromagnetic
susceptibility:
Designed to meet IEC 801, -2, -3, -4, -5, -6, Level 3
Humidity:
Vibration:
MTBF demonstrated:
Operating; non-condensing 5% to 95% RH
Three orthogonal axes, sweep at 1 oct/min, 5 min. dwell at four major resonances 0.75G peak 5Hz
to 500Hz, operational
> 550,000 hours at full load and 25 °C ambient conditions
Rev. 7.8.09_4
LPS40 Series
 of 3
Ordering Information
Model Number
Output Minimum Maximum Load with
Voltage Load Convection Cooling
Maximum Load with
30CFM Forced Air
Peak Load 1 Regulation 2 Ripple P/P (PARD)3
LPS41(-T)
3.3 V
0A
8A
11 A
12 A
LPS42(-T)
5V
0A
8A
11 A
12 A
LPS43(-T)
12 V
0A
3.3 A
4.5 A
5A
LPS44(-T)
15 V
0A
2.6 A
3.6 A
4A
LPS45(-T)
24 V
0A
1.7 A
2.3 A
2.5 A
LPS48(-T)
48 V
0A
0.9 A
1.2 A
1.3 A
1. Peak current lasting < 30 seconds with a maximum 10% duty cycle.
2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
± 2%
± 2%
± 2%
± 2%
± 2%
± 2%
50 mV
50 mV
120 mV
150mV
240mV
480 mV­
3. Peak-to-peak with 20 MHz bandwidth and 10 µF in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
4. (-T) indicates Terminal Block option for input and output (instead of Molex type)
Power Derating Curve
55W
30 CFM Forced Air Cooling
40W
Output 30W
Power
(Watts) 20W
Natural
Convection
Cooling
27.5W
20W
10W
0W
0°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C
TA – Ambient Temperature – °C