English
Language : 

LPS202-M Datasheet, PDF (2/3 Pages) Emerson Network Power – Medical and ITE safeties
Embedded Power for
Business-Critical Continuity
Environmental Specifications
Operating temperature:
Storage temperature:
Electromagnetic
susceptibility:
Humidity:
Vibration:
MTBF demonstrated:
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C
start up
-40 °C to +85 °C
Designed to meet EN61000-4;
-2, -3, -4, -5, -6, -8, -11 Level 3
Operating; non-condensing 10% to 95% RH
IEC68-2-6 to the levels of IEC721-3-2
>550,000 hours at full load and 25 °C ambient conditions
Ordering Information
Model
Number
Output Minimum Maximum Load with
Voltage
Load
Convection Cooling
Maximum Load with
30CFM Forced Air
Peak Load Regulation2
Ripple
P/P (PARD)3
LPS202-M
LPS203-M
LPS204-M
LPS205-M
5V
0A
12 V
0A
15 V
0A
24 V
0A
20 A
10.3 A
8.3 A
5.2 A
40 A
20.8 A
16.6 A
10.4 A
44 A
±2%
22 A
±2%
18 A
±2%
11.5 A
±2%
50 mV
120 mV
150 mV
240 mV
LPS208-M
48 V
0A
2.6 A
5.2 A
5.8 A
±2%
480 mV
1. Peak current lasting <30 seconds with a maximum 10% duty cycle.
2­. At 25°C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3­. Peak-to-peak with 20 mHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
Rev. 7.9.09_#98
LPS200-M Series
 of 3
Pin Assignments
Connector LPS200-M
SK1
Pin 1
Neutral
Pin 3
Line
SK2
TB-1
Common
TB-2
Main output
SK3
Pin 1
+V1 Remote sense
Pin 2
-V1 Remote sense
Pin 3
N/C
Pin 4
N/C
Pin 5
+Power fail
Pin 6
Common
Pin 7
N/C
Pin 8
Common
Pin 9
+12 V Fan
Pin 10 +12 Fan Return (isolated)
Mating­ Connectors
AC Input (SK1): Molex 09-50-8031 (connector)
PINS:08-52-0113
AC Ground: Molex 01-90020001
DC Output
(SK2):
Molex 19141-0058/0063/0083
Spade lug based on Cable Ampacity/AWG
Control Signals Molex 90142-0010 (USA)
(SK3):
PINS:90119-2110 or
Amp: 87977-3
PINS: 87309-8
Emerson Network Power Connector Kit #70-841-020, includes all of the
above.
1. Specifications subject to change without notice.
­2. All dimensions in inches (mm), tolerance is ±0.02”­­ (±0.5mm)
3. Mounting holes MH1 and MH2 should be grounded for EMI purposes.
4. Mounting hole MH1 is safety ground connection.
5. Specifications are for convection rating at factory settings at 115 VAC
input, 25 °C unless otherwise stated.
6. This power supply requires mounting on metal
standoffs 0.20” (5m) in height.
7. Warranty:2 years
8. Weight: 0.75 lb/0.34 kg