UMP Datasheet, PDF (1/6 Pages) Emerson Network Power – μMP Series | |||
|
Embedded Power for
Business-Critical Continuity
µMP Series
Up to 1200 Watts
MicroMP 1U Multi Output
Rev. 07.18.11_10
µMP Series
1 of 6
Total Power: Up to 1200 Watts
Input Voltage: 85 - 264 Vac
120-300 Vdc
# of Outputs: Up to 12
Special Features
⢠Full Medical EN60601 approval
⢠PMBus
⢠High efficiency
⢠Current limit modification
(foldback or constant current)
⢠High power density.
uMP4: 10.8 W/cu-in
uMP1: 15.1 W/cu-in
⢠Intelligent fan
(speed control/fault status)
⢠Downloadable GUI from website
⢠uP controlled PFC input with active
inrush protection
⢠Optional conformal coating
⢠Industrial temp range (-40 ºC to 70 ºC)
⢠No preload required
⢠Industrial shock/vibration (> 50Gâs)
⢠Low cost
⢠IEC or terminal block input
⢠Low profile 1U size
Safety
⢠UL
⢠CSA
⢠VDE
⢠BABT
⢠CB
⢠CE
⢠CCC
⢠BSMI
UL60950/UL60601-1
CSA22.2 No. 234 Level 5
EN60950/EN60601-1
Compliance to
EN60950/EN60601 BS7002
Certificate and report
Mark to LVD
Approved
Approved
Electrical Specifications
µMP4C shown
Input
Input raÂnge:
85 - 264 Vac, 120 - 350 Vdc (limited to 250 Vac/300 Vdc in medical apps)
Frequency:
47 - 440 Hz
Inrush current:
40 A peak max. (soft start)
Efficiency:
Up to 91% @ full case load
Power Factor:
Turn-on time:
0.99 typ. meets EN61000-3-2 (n/a @ 440 Hz)
AC on 2 sec for uMP1 and 1.5 sec for uMP4, inhibit/enable 250 ms typical
EMI filter:
CISPR 22/EN55022 Level âBâ
Leakage current:
Radiated EMI:
Holdover storage:
AC OK:
Harmonic distortion:
300 µA max. @ 240 Vac for uMP1 and 500 µA max for uMP4; 47 - 63 Hz
CISPR 22/EN55022 Level âBâ
16.7 ms minimum (independent of input Vac, 0 °C to 50 °C))
Signal goes low indicating loss of AC input.
Hold up = Full cycle ride thru (50 Hz)
Meets EN61000-3-2
Isolation:
Meets EN60950 and EN60601
Global Inhibit/Enable: TTL, Logic â1â and Logic â0â; fan off when unit is inhibited
Input fuse (internal): uMP1: 16 A/250 V TLAG, uMP4: 10 A / 250 V. (both lines fused)
Warranty:
2 years
Environmental Specifications
Operating temperature:
-40 ° to 70 °C ambient. Derate each output 2.5% per degree from 50 °C to 70 °C.
( -20 °C start up). Meets full spec after 1/2 load. 10 min warm-up
Storage temperature:
-40 °C to 85 °C
Electromagnetic susceptibility: Designed to meet EN61000-4; Â-3, -6, -11 Level 3, Level 4 for -2, -4, -5
Humidity:
Operating; non-condensing 10% to 95% RH
Vibration:
MIL-STD-810E
MTBF demonstrated:
> 350,000 hours at full load, one uMP4 case + two modules, Telcordia SR-332
Altitude:
calculated MTBF