English
Language : 

IMP Datasheet, PDF (1/8 Pages) Power-One – 1...12 Watt DC-DC Converters
Embedded Power for
Business-Critical Continuity
Intelligent MP
Series
Up to 1500 Watts
Total Power: Up to 1500 Watts
Input Voltage: 85 - 264 VAC
120-300 VDC
# of Outputs: Up to 21
Special Features
• Full Medical EN60601 approval
• Intelligent I2C control
• Voltage adjustment on all outputs
(Manual or I2C)
• Configurable input and output
(case and module) OK signals and
indicators
• Configurable inhibit/enable
• Configurable output
UP/DOWN sequencing
• Configurable current limit
(foldback or constant current)
• High power density (8.8 W/cu-in)
• Intelligent fan
(speed control/fault status)
• Downloadable GUI from website
• Customer provided air option
• uP controlled PFC input with active
inrush protection
• I2C monitor of voltage, current, and
temp
• Programmable voltage, current limit,
inhibit/enable through I2C
• Optional extended hold-up module
(SEMI F47 compliance)
• Increased power density to 50% over
standard MP
• External switching frequency sync
input
• Optional conformal coating
• Industrial temp range (-40 ºC to 70 ºC)
• No preload required
• Industrial shock/vibration (>50G’s)
Safety
UL UL60950/UL2601
CSA CSA22.2 No. 234 Level 5
VDE EN60950/EN60601-1
BABT Compliance to
EN60950/EN60601 BS7002
CB Certificate and report
CE Mark to LVD
TM
Font: Minion Bold for MP
Minion italic for i ; size for each is the same
Created on Mac
Color: "i" 100% Blue, 50% Magenta,
0% Yellow, 0% Black
"MP" - 100% Black
Rev. 10.09.08_77
iMP Series
 of 8
Electrical Specifications
Input
Input ra­nge:
Frequency:
85-264 Vac 120-350 Vdc
(limited to 300 Vdc in medical applications)
47-440 Hz
Inrush current:
40 A peak max. (soft start)
Efficiency:
Up to 85% @ full case load
Power Factor:
0.99 typ. meets EN61000-3-2 (n/a @ 440 Hz)
Turn-on time:
EMI filter:
AC on 2.0 sec typ., inhibit/enable 150ms typical
Programmable delay; 50ms internal turn-on delay (Dual Output only)
CISPR 22/EN55022 Level “B”
Leakage current:
300µA max. @ 240 Vac; 47 - 63 Hz
Radiated EMI:
Holdover storage:
AC OK:
Harmonic distortion:
Isolation:
CISPR 22/EN55022 Level “B”
20 ms minimum (independent of input Vac) additional 34ms holdover
storage with optional HUP module
(SEMI F47 compatible). For iMP4 15 ms (low-line), 10 ms (high-line)
>5 ms early warning min. before outputs lose regulation
Full cycle ride thru (50 Hz) (n/a on iMP4> 750 W @ 90 Vac)
Meets EN61000-3-2
Meets EN60950 and EN60601
Global Inhibit/Enable: TTL, Logic “1” and Logic “0”; configurable
Input fuse (internal): iMP4: 16 A; iMP8: 20 A; iMP1: 25 A (both lines fused)
Warranty:
2 years