DS1500-3 Datasheet, PDF (1/4 Pages) Astec America, Inc – 1500 Watts 12V Distributed Power System | |||
|
Embedded Power for
Business-Critical Continuity
DS1500-3
1500 Watts 12V
Distributed Power System
Distributed Power Bulk Front-End
Total Output Power: 1500 Watts
+12vdc Main Output;
+3.3vdc Stand-by Output
Wide Range Input voltage: 90 - 264VAC
180 - 264vac 1500w
90 - 264vac 910W
Special Features
⢠Active Power Factor Correction
⢠EN61000-3-2 Harmonic
Compliance
⢠Active AC Inrush Control
⢠2U X 3U Form Factor 7.5" long
⢠15W/ in3
⢠+12vdc Output
⢠+3.3vdc Stand-By
⢠Hot Plug Operation
⢠N + 1 Redundant
⢠Internal OR'ing Main and Stand-by
⢠Active Current Sharing
⢠Internal Cooling Fans
(60mm x 38mm)
⢠I2C Communication Interface Bus
⢠EERPOM for FRU Data
⢠Green LED Status, Power OK
⢠Amber LED Status, Power Failed
⢠Internal Fan Speed Control
⢠Fan Fail Output Signal
⢠INTEL, SSI Std. Logic Timing
⢠INTEL, SSI Std. FRU Data Format
⢠AC shutdown <85VAC or 170VAC
⢠One Year Warranty
Safety
UL/cUL 60950 (UL Recognized)
1st edition (UL)60950-1-03 CSA
NEMKO+ CB Report EN60950
EN60950
CE Mark
China CCC
CB Test Report
Electrical Specifications
Input
Input range
Frequency
Inrush current
Efficiency
90-264 VAC, 910w
180 - 264 vac, 1500w
47-63 Hz, single phase AC
35A maximum inrush current
>80% typical at full load, high line
Conducted EMI
FCC Subpart J EN55022 Class A
Radiated EMI
FCC Subpart J EN55022 Class A
Power factor
0.99 typical
Leakage current
0.75mA @ 240VAC
Hold up time
12ms minimum
Output
Main DC voltage
+12v @ 74A (90VAC) or 123A (180VAC)
Stand-By
+3.3vsb @ 7A
Adjustment range
Regulation
Over current
Over voltage
Under voltage
Factory Set, no pot adjustments
+12vdc; ±3%; +3.3vsb; ±3%
+12vdc; 110 - 130%
latches off if overcurrent lasts over 1.5 seconds,
otherwise it is auto recovery.
+3.3vsb, 7A - 105% - 130%
+12vdc; 13.7v ±7%
+3.3vsb; 4.0v ±7%
+12vdc; 11.0 - 11.4vdc
Turn-on delay
+12vOutput Rise Time
I Share 12V
<3 Second max
5 - <200mS, Monotonic Rise
15% from 50 - 100% load
Rev. 01.11.06
DS1500-3
1 of 4
|
▷ |