English
Language : 

W2E143-AB09-06 Datasheet, PDF (5/5 Pages) ebm-papst – AC axial compact fan
W2E143-AB09-06
AC axial compact fan
Charts: Air flow 60 Hz
0
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
0
pfs @ rho=1,2 kg/m³
qv [CFM]
20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
0,75
0,7
0,65
0,6
0,55
0,5
0,45
0,4
4
0,35
0,3
3
0,25
0,2
2
0,15
0,1
0,05
1
0
50
100 150 200 250 300 350 400 450 500
qv [m³/h]
Measured values
U
f
n
Pe
I
qv
pfs
V
Hz
min-1 W
A
m3/h Pa
1
230 60
3300 29
0.13 490 0
2
230 60
3210 31
0.14 445 30
3
230 60
3175 32
0.14 380 60
4
230 60
3140 33
0.14 290 85
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Measurement: LU-58510
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Item no. 11174-5-9980 · Revision 80549 · Release 2014-07-23 · Page 5 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com