TECHNICAL DATASHEET
Sync DIN Rail Power Supply
24V 30W 1 Phase (NEC Class 2) / DRS-24V30W1NZ
Safety Instructions
– ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the device. If mains are not turned OFF,
there is risk of explosion / severe damage.
– To guarantee sufficient convection cooling, keep a distance of 80mm
(3.14 inch) above and below the device as well as a lateral distance of
25mm (0.98 inch) to other units.
– Note that the enclosure of the device can become very hot depending on
the surrounding air temperature and output load connected to the device.
Risk of burns!
– The main power must be turned off before connecting or disconnecting the
wires to the terminals!
– DO NOT insert any objects into the device.
– Dangerous voltages present for at least 5 minutes after disconnecting all
sources of power.
– The power supplies unit should be installed in minimum IP54 rated
enclosure.
– The power supplies are built in units and must be installed in a cabinet or
room (condensation free environment and indoor location) that is relatively
free of conductive contaminants.
9
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.