English
Language : 

DRC-24V60W1AZ Datasheet, PDF (8/11 Pages) Delta Electronics, Inc. – Power will not de-rate for the entire input voltage range
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 60W 1 Phase (Class II & NEC Class 2) / DRC-24V60W1AZ
Safety Instructions
– ALWAYS switch mains of input power OFF before connecting and
disconnecting the input voltage to the unit. If mains are not turned
OFF, there is risk of explosion / severe damage.
– To guarantee sufficient convection cooling, keep a distance
of 50mm above and below the device as well as a lateral
distance of 25mm to other units.
– Note that the enclosure of the device can become very hot
depending on the surrounding air temperature and load of the
power supply. Risk of burns!
– DO NOT insert any objects into the unit.
– Hazardous voltages may be present for up to 5 minutes after the
input mains voltage is disconnected. Do not touch the unit during
this time.
– The power supplies unit should be installed in minimum IP54 rated
enclosure.
– The power supplies are built in units and must be installed in a
cabinet or room (condensation free environment and indoor
location) that is relatively free of conductive contaminants.
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time
required for the output to reach 90% of its set value, after the input voltage is removed.
8
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (July 2014, Rev. 00)